🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 75 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.81%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.23V (18.58%)
Voltage at Load End11.7 VLoss: 0.34 V (236.6 W)
Power & Breaker (125%)8.4 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 75 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A329.27 V (2743.93%)0.0 V543.14 V (4526.21%)230490.3 WDrop/Amp High
12 AWG3.31 mm²20 A206.91 V (1724.28%)0.0 V341.31 V (2844.26%)144839.9 WDrop/Amp High
10 AWG5.26 mm²30 A130.21 V (1085.05%)0.0 V214.78 V (1789.83%)91144.5 WDrop/Amp High
8 AWG8.37 mm²50 A81.83 V (681.89%)0.0 V134.98 V (1124.79%)57278.4 WDrop/Amp High
6 AWG13.3 mm²65 A51.5 V (429.13%)0.0 V84.94 V (707.86%)36046.6 WDrop/Amp High
4 AWG21.15 mm²85 A32.38 V (269.85%)0.0 V53.42 V (445.13%)22667.6 WDrop/Amp High
3 AWG26.67 mm²100 A25.68 V (214.0%)0.0 V42.36 V (353.0%)17976.0 WDrop/Amp High
2 AWG33.62 mm²115 A20.37 V (169.76%)0.0 V33.6 V (280.03%)14260.0 WDrop/Amp High
1 AWG42.41 mm²130 A16.15 V (134.58%)0.0 V26.64 V (221.99%)11304.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.8 V (106.7%)0.0 V21.12 V (176.01%)8962.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.16 V (84.64%)1.8 V16.75 V (139.62%)7109.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.06 V (67.14%)3.9 V13.29 V (110.75%)5639.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.39 V (53.24%)5.6 V10.54 V (87.82%)4472.2 WDrop/Amp High
250 kcmil126.7 mm²255 A5.41 V (45.05%)6.6 V8.92 V (74.31%)3783.9 WDrop/Amp High
300 kcmil152.0 mm²285 A4.51 V (37.55%)7.5 V7.43 V (61.94%)3154.1 WDrop/Amp High
350 kcmil177.3 mm²310 A3.86 V (32.19%)8.1 V6.37 V (53.1%)2704.0 WDrop/Amp High
400 kcmil202.7 mm²335 A3.38 V (28.16%)8.6 V5.57 V (46.45%)2365.2 WDrop/Amp High
500 kcmil253.4 mm²380 A2.7 V (22.52%)9.3 V4.46 V (37.15%)1891.9 WDrop/Amp High
600 kcmil304.0 mm²420 A2.25 V (18.77%)9.7 V3.72 V (30.97%)1577.0 WDrop/Amp High
750 kcmil380.0 mm²475 A1.8 V (15.02%)10.2 V2.97 V (24.78%)1261.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.35 V (11.26%)10.6 V2.23 V (18.58%)946.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 75 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 75 feet one-way at 12V (DC), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.81%) and delivers 11.7V at the load.

What size aluminum wire is required for 700 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.23V (18.58%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.