🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 175 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)9× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.92%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.2V (43.35%)
Voltage at Load End11.7 VLoss: 0.35 V (245.3 W)
Power & Breaker (125%)8.4 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 175 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A768.3 V (6402.51%)0.0 V1267.34 V (10561.15%)537810.8 WDrop/Amp High
12 AWG3.31 mm²20 A482.8 V (4023.33%)0.0 V796.39 V (6636.61%)337959.7 WDrop/Amp High
10 AWG5.26 mm²30 A303.81 V (2531.79%)0.0 V501.15 V (4176.27%)212670.4 WDrop/Amp High
8 AWG8.37 mm²50 A190.93 V (1591.07%)0.0 V314.94 V (2624.51%)133649.5 WDrop/Amp High
6 AWG13.3 mm²65 A120.16 V (1001.29%)0.0 V198.2 V (1651.67%)84108.8 WDrop/Amp High
4 AWG21.15 mm²85 A75.56 V (629.66%)0.0 V124.64 V (1038.64%)52891.1 WDrop/Amp High
3 AWG26.67 mm²100 A59.92 V (499.33%)0.0 V98.84 V (823.67%)41944.0 WDrop/Amp High
2 AWG33.62 mm²115 A47.53 V (396.11%)0.0 V78.41 V (653.4%)33273.2 WDrop/Amp High
1 AWG42.41 mm²130 A37.68 V (314.01%)0.0 V62.16 V (517.97%)26377.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A29.88 V (248.97%)0.0 V49.28 V (410.68%)20913.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A23.7 V (197.5%)0.0 V39.09 V (325.78%)16589.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A18.8 V (156.65%)0.0 V31.01 V (258.41%)13159.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A14.91 V (124.23%)0.0 V24.59 V (204.92%)10435.1 WDrop/Amp High
250 kcmil126.7 mm²255 A12.61 V (105.11%)0.0 V20.81 V (173.38%)8829.1 WDrop/Amp High
300 kcmil152.0 mm²285 A10.51 V (87.61%)1.5 V17.34 V (144.52%)7359.5 WDrop/Amp High
350 kcmil177.3 mm²310 A9.01 V (75.11%)3.0 V14.87 V (123.9%)6309.3 WDrop/Amp High
400 kcmil202.7 mm²335 A7.88 V (65.7%)4.1 V13.0 V (108.37%)5518.7 WDrop/Amp High
500 kcmil253.4 mm²380 A6.31 V (52.55%)5.7 V10.4 V (86.69%)4414.5 WDrop/Amp High
600 kcmil304.0 mm²420 A5.26 V (43.81%)6.7 V8.67 V (72.26%)3679.8 WDrop/Amp High
750 kcmil380.0 mm²475 A4.21 V (35.05%)7.8 V6.94 V (57.81%)2943.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.15 V (26.28%)8.8 V5.2 V (43.35%)2207.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 175 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 175 feet one-way at 12V (DC), you need 9× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.92%) and delivers 11.7V at the load.

What size aluminum wire is required for 700 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.2V (43.35%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.