⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 80 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)5× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.4%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.38V (19.82%)
Voltage at Load End11.7 VLoss: 0.29 V (201.8 W)
Power & Breaker (125%)8.4 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 80 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A351.22 V (2926.86%)0.0 V579.35 V (4827.95%)245856.4 WDrop/Amp High
12 AWG3.31 mm²20 A220.71 V (1839.24%)0.0 V364.07 V (3033.88%)154495.8 WDrop/Amp High
10 AWG5.26 mm²30 A138.89 V (1157.39%)0.0 V229.1 V (1909.15%)97220.8 WDrop/Amp High
8 AWG8.37 mm²50 A87.28 V (727.34%)0.0 V143.97 V (1199.78%)61096.9 WDrop/Amp High
6 AWG13.3 mm²65 A54.93 V (457.73%)0.0 V90.61 V (755.05%)38449.7 WDrop/Amp High
4 AWG21.15 mm²85 A34.54 V (287.84%)0.0 V56.98 V (474.81%)24178.8 WDrop/Amp High
3 AWG26.67 mm²100 A27.39 V (228.27%)0.0 V45.18 V (376.53%)19174.4 WDrop/Amp High
2 AWG33.62 mm²115 A21.73 V (181.08%)0.0 V35.84 V (298.7%)15210.6 WDrop/Amp High
1 AWG42.41 mm²130 A17.23 V (143.55%)0.0 V28.41 V (236.79%)12058.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.66 V (113.81%)0.0 V22.53 V (187.74%)9560.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.83 V (90.28%)1.2 V17.87 V (148.93%)7583.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.59 V (71.61%)3.4 V14.18 V (118.13%)6015.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.81 V (56.79%)5.2 V11.24 V (93.68%)4770.3 WDrop/Amp High
250 kcmil126.7 mm²255 A5.77 V (48.05%)6.2 V9.51 V (79.26%)4036.2 WDrop/Amp High
300 kcmil152.0 mm²285 A4.81 V (40.05%)7.2 V7.93 V (66.07%)3364.4 WDrop/Amp High
350 kcmil177.3 mm²310 A4.12 V (34.34%)7.9 V6.8 V (56.64%)2884.3 WDrop/Amp High
400 kcmil202.7 mm²335 A3.6 V (30.03%)8.4 V5.95 V (49.54%)2522.8 WDrop/Amp High
500 kcmil253.4 mm²380 A2.88 V (24.02%)9.1 V4.76 V (39.63%)2018.1 WDrop/Amp High
600 kcmil304.0 mm²420 A2.4 V (20.03%)9.6 V3.96 V (33.03%)1682.2 WDrop/Amp High
750 kcmil380.0 mm²475 A1.92 V (16.02%)10.1 V3.17 V (26.43%)1345.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.44 V (12.01%)10.6 V2.38 V (19.82%)1009.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 80 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 80 feet one-way at 12V (DC), you need 5× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.29V (2.4%) and delivers 11.7V at the load.

What size aluminum wire is required for 700 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.38V (19.82%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.