750 Amp Wire Size at 300 Feet (240V Three-Phase (US Industrial Delta))
Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 300 ft (91.4 m) one-way run.
Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.04%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.28V (3.45%)
Voltage at Load End237.5 VLoss: 2.51 V (3258.4 W)
Power & Breaker (125%)311.77 kW1000A Breaker Recommended
All AWG & kcmil Wire Gauges for 750 Amps at 300 Feet (240V)
| Wire Gauge | Metric Area | NEC 75°C Cu Ampacity | Copper Voltage Drop | Load Voltage | Aluminum Drop | Line Loss ($I^2R$) | NEC Status |
|---|---|---|---|---|---|---|---|
| 14 AWG | 2.08 mm² | 15 A | 1222.11 V (509.21%) | 0.0 V | 2015.9 V (839.96%) | 1587561.1 W | Drop/Amp High |
| 12 AWG | 3.31 mm² | 20 A | 767.97 V (319.99%) | 0.0 V | 1266.79 V (527.83%) | 997621.5 W | Drop/Amp High |
| 10 AWG | 5.26 mm² | 30 A | 483.27 V (201.36%) | 0.0 V | 797.16 V (332.15%) | 627780.8 W | Drop/Amp High |
| 8 AWG | 8.37 mm² | 50 A | 303.7 V (126.54%) | 0.0 V | 500.96 V (208.74%) | 394519.4 W | Drop/Amp High |
| 6 AWG | 13.3 mm² | 65 A | 191.13 V (79.64%) | 48.9 V | 315.27 V (131.36%) | 248280.2 W | Drop/Amp High |
| 4 AWG | 21.15 mm² | 85 A | 120.19 V (50.08%) | 119.8 V | 198.25 V (82.61%) | 156128.9 W | Drop/Amp High |
| 3 AWG | 26.67 mm² | 100 A | 95.31 V (39.71%) | 144.7 V | 157.22 V (65.51%) | 123814.3 W | Drop/Amp High |
| 2 AWG | 33.62 mm² | 115 A | 75.61 V (31.5%) | 164.4 V | 124.72 V (51.97%) | 98219.1 W | Drop/Amp High |
| 1 AWG | 42.41 mm² | 130 A | 59.94 V (24.97%) | 180.1 V | 98.87 V (41.2%) | 77862.0 W | Drop/Amp High |
| 1/0 AWG | 53.49 mm² | 150 A | 47.52 V (19.8%) | 192.5 V | 78.39 V (32.66%) | 61733.5 W | Drop/Amp High |
| 2/0 AWG | 67.43 mm² | 175 A | 37.7 V (15.71%) | 202.3 V | 62.18 V (25.91%) | 48971.2 W | Drop/Amp High |
| 3/0 AWG | 85.01 mm² | 200 A | 29.9 V (12.46%) | 210.1 V | 49.32 V (20.55%) | 38844.0 W | Drop/Amp High |
| 4/0 AWG | 107.2 mm² | 230 A | 23.71 V (9.88%) | 216.3 V | 39.11 V (16.3%) | 30803.4 W | Drop/Amp High |
| 250 kcmil | 126.7 mm² | 255 A | 20.06 V (8.36%) | 219.9 V | 33.09 V (13.79%) | 26062.6 W | Drop/Amp High |
| 300 kcmil | 152.0 mm² | 285 A | 16.72 V (6.97%) | 223.3 V | 27.59 V (11.49%) | 21724.5 W | Drop/Amp High |
| 350 kcmil | 177.3 mm² | 310 A | 14.34 V (5.97%) | 225.7 V | 23.65 V (9.85%) | 18624.5 W | Drop/Amp High |
| 400 kcmil | 202.7 mm² | 335 A | 12.54 V (5.23%) | 227.5 V | 20.69 V (8.62%) | 16290.7 W | Drop/Amp High |
| 500 kcmil | 253.4 mm² | 380 A | 10.03 V (4.18%) | 230.0 V | 16.55 V (6.89%) | 13031.3 W | Drop/Amp High |
| 600 kcmil | 304.0 mm² | 420 A | 8.36 V (3.48%) | 231.6 V | 13.79 V (5.75%) | 10862.3 W | Drop/Amp High |
| 750 kcmil | 380.0 mm² | 475 A | 6.69 V (2.79%) | 233.3 V | 11.03 V (4.6%) | 8689.8 W | Drop/Amp High |
| 1000 kcmil | 506.7 mm² | 545 A | 5.02 V (2.09%) | 235.0 V | 8.28 V (3.45%) | 6516.9 W | Drop/Amp High |
Frequently Asked Engineering Questions
What size copper wire do I need for 750 amps at 300 feet (240V)?
To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 300 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.51V (1.04%) and delivers 237.5V at the load.
What size aluminum wire is required for 750 amps at 300 feet?
Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.28V (3.45%).
What breaker size is needed for a 750A continuous load?
Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.