🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

750 Amp Wire Size at 50 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.17%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.38V (0.57%)
Voltage at Load End239.6 VLoss: 0.42 V (543.1 W)
Power & Breaker (125%)311.77 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 50 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A203.68 V (84.87%)36.3 V335.98 V (139.99%)264593.5 WDrop/Amp High
12 AWG3.31 mm²20 A127.99 V (53.33%)112.0 V211.13 V (87.97%)166270.2 WDrop/Amp High
10 AWG5.26 mm²30 A80.54 V (33.56%)159.5 V132.86 V (55.36%)104630.1 WDrop/Amp High
8 AWG8.37 mm²50 A50.62 V (21.09%)189.4 V83.49 V (34.79%)65753.2 WDrop/Amp High
6 AWG13.3 mm²65 A31.85 V (13.27%)208.1 V52.54 V (21.89%)41380.0 WDrop/Amp High
4 AWG21.15 mm²85 A20.03 V (8.35%)220.0 V33.04 V (13.77%)26021.5 WDrop/Amp High
3 AWG26.67 mm²100 A15.89 V (6.62%)224.1 V26.2 V (10.92%)20635.7 WDrop/Amp High
2 AWG33.62 mm²115 A12.6 V (5.25%)227.4 V20.79 V (8.66%)16369.9 WDrop/Amp High
1 AWG42.41 mm²130 A9.99 V (4.16%)230.0 V16.48 V (6.87%)12977.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.92 V (3.3%)232.1 V13.06 V (5.44%)10288.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.28 V (2.62%)233.7 V10.36 V (4.32%)8161.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.98 V (2.08%)235.0 V8.22 V (3.43%)6474.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.95 V (1.65%)236.0 V6.52 V (2.72%)5133.9 WDrop/Amp High
250 kcmil126.7 mm²255 A3.34 V (1.39%)236.7 V5.52 V (2.3%)4343.8 WDrop/Amp High
300 kcmil152.0 mm²285 A2.79 V (1.16%)237.2 V4.6 V (1.92%)3620.8 WDrop/Amp High
350 kcmil177.3 mm²310 A2.39 V (1.0%)237.6 V3.94 V (1.64%)3104.1 WDrop/Amp High
400 kcmil202.7 mm²335 A2.09 V (0.87%)237.9 V3.45 V (1.44%)2715.1 WDrop/Amp High
500 kcmil253.4 mm²380 A1.67 V (0.7%)238.3 V2.76 V (1.15%)2171.9 WDrop/Amp High
600 kcmil304.0 mm²420 A1.39 V (0.58%)238.6 V2.3 V (0.96%)1810.4 WDrop/Amp High
750 kcmil380.0 mm²475 A1.11 V (0.46%)238.9 V1.84 V (0.77%)1448.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.84 V (0.35%)239.2 V1.38 V (0.57%)1086.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 50 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 50 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.42V (0.17%) and delivers 239.6V at the load.

What size aluminum wire is required for 750 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.38V (0.57%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.