⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

750 Amp Wire Size at 600 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 750 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.41%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 19.11V (15.93%)
Voltage at Load End117.1 VLoss: 2.9 V (2172.3 W)
Power & Breaker (125%)90.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 750 Amps at 600 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2822.33 V (2351.94%)0.0 V4655.53 V (3879.61%)2116748.1 WDrop/Amp High
12 AWG3.31 mm²20 A1773.55 V (1477.96%)0.0 V2925.53 V (2437.94%)1330161.9 WDrop/Amp High
10 AWG5.26 mm²30 A1116.05 V (930.05%)0.0 V1840.97 V (1534.14%)837041.1 WDrop/Amp High
8 AWG8.37 mm²50 A701.37 V (584.47%)0.0 V1156.93 V (964.11%)526025.8 WDrop/Amp High
6 AWG13.3 mm²65 A441.39 V (367.82%)0.0 V728.08 V (606.74%)331040.3 WDrop/Amp High
4 AWG21.15 mm²85 A277.56 V (231.3%)0.0 V457.85 V (381.54%)208171.9 WDrop/Amp High
3 AWG26.67 mm²100 A220.11 V (183.43%)0.0 V363.09 V (302.57%)165085.7 WDrop/Amp High
2 AWG33.62 mm²115 A174.61 V (145.51%)0.0 V288.03 V (240.02%)130958.8 WDrop/Amp High
1 AWG42.41 mm²130 A138.42 V (115.35%)0.0 V228.33 V (190.28%)103816.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A109.75 V (91.46%)10.3 V181.03 V (150.86%)82311.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A87.06 V (72.55%)32.9 V143.61 V (119.67%)65294.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A69.06 V (57.55%)50.9 V113.91 V (94.93%)51792.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A54.76 V (45.63%)65.2 V90.33 V (75.28%)41071.2 WDrop/Amp High
250 kcmil126.7 mm²255 A46.33 V (38.61%)73.7 V76.43 V (63.69%)34750.1 WDrop/Amp High
300 kcmil152.0 mm²285 A38.62 V (32.18%)81.4 V63.71 V (53.09%)28966.0 WDrop/Amp High
350 kcmil177.3 mm²310 A33.11 V (27.59%)86.9 V54.62 V (45.51%)24832.7 WDrop/Amp High
400 kcmil202.7 mm²335 A28.96 V (24.13%)91.0 V47.77 V (39.81%)21720.9 WDrop/Amp High
500 kcmil253.4 mm²380 A23.17 V (19.31%)96.8 V38.21 V (31.85%)17375.0 WDrop/Amp High
600 kcmil304.0 mm²420 A19.31 V (16.09%)100.7 V31.85 V (26.54%)14483.0 WDrop/Amp High
750 kcmil380.0 mm²475 A15.45 V (12.87%)104.6 V25.48 V (21.24%)11586.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A11.59 V (9.65%)108.4 V19.11 V (15.93%)8689.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 750 amps at 600 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 750A load over 600 feet one-way at 120V (1-Phase), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.9V (2.41%) and delivers 117.1V at the load.

What size aluminum wire is required for 750 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 19.11V (15.93%).

What breaker size is needed for a 750A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (750A × 1.25 = 937.5A), which corresponds to a standard 1000A circuit breaker.