🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 40 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 0.82%
Aluminum Wire (≤3% Drop)2 AWGDrop: 2.05V (0.85%)
Voltage at Load End238.0 VLoss: 1.97 V (157.9 W)
Power & Breaker (125%)19.2 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 40 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A20.07 V (8.36%)219.9 V33.11 V (13.79%)1605.6 WDrop/Amp High
12 AWG3.31 mm²20 A12.61 V (5.25%)227.4 V20.8 V (8.67%)1009.0 WDrop/Amp High
10 AWG5.26 mm²30 A7.94 V (3.31%)232.1 V13.09 V (5.45%)634.9 WDrop/Amp High
8 AWG8.37 mm²50 A4.99 V (2.08%)235.0 V8.23 V (3.43%)399.0 WDrop/Amp High
6 AWG13.3 mm²65 A3.14 V (1.31%)236.9 V5.18 V (2.16%)251.1 WDrop/Amp High
4 AWG21.15 mm²85 A1.97 V (0.82%)238.0 V3.26 V (1.36%)157.9 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.57 V (0.65%)238.4 V2.58 V (1.08%)125.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.24 V (0.52%)238.8 V2.05 V (0.85%)99.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.98 V (0.41%)239.0 V1.62 V (0.68%)78.7 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.78 V (0.33%)239.2 V1.29 V (0.54%)62.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.62 V (0.26%)239.4 V1.02 V (0.43%)49.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.49 V (0.2%)239.5 V0.81 V (0.34%)39.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.39 V (0.16%)239.6 V0.64 V (0.27%)31.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.33 V (0.14%)239.7 V0.54 V (0.23%)26.4 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.27 V (0.11%)239.7 V0.45 V (0.19%)22.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.24 V (0.1%)239.8 V0.39 V (0.16%)18.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.21 V (0.09%)239.8 V0.34 V (0.14%)16.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.16 V (0.07%)239.8 V0.27 V (0.11%)13.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.14 V (0.06%)239.9 V0.23 V (0.09%)11.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.11 V (0.05%)239.9 V0.18 V (0.08%)8.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.08 V (0.03%)239.9 V0.14 V (0.06%)6.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 40 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 40 feet one-way at 240V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 1.97V (0.82%) and delivers 238.0V at the load.

What size aluminum wire is required for 80 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 2.05V (0.85%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.