⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 100 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.18%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.94V (0.61%)
Voltage at Load End479.1 VLoss: 0.89 V (1235.8 W)
Power & Breaker (125%)665.11 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 100 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A434.53 V (90.53%)45.5 V716.77 V (149.33%)602097.2 WDrop/Amp High
12 AWG3.31 mm²20 A273.06 V (56.89%)206.9 V450.41 V (93.84%)378357.2 WDrop/Amp High
10 AWG5.26 mm²30 A171.83 V (35.8%)308.2 V283.44 V (59.05%)238091.7 WDrop/Amp High
8 AWG8.37 mm²50 A107.98 V (22.5%)372.0 V178.12 V (37.11%)149625.1 WDrop/Amp High
6 AWG13.3 mm²65 A67.96 V (14.16%)412.0 V112.1 V (23.35%)94162.6 WDrop/Amp High
4 AWG21.15 mm²85 A42.73 V (8.9%)437.3 V70.49 V (14.69%)59213.3 WDrop/Amp High
3 AWG26.67 mm²100 A33.89 V (7.06%)446.1 V55.9 V (11.65%)46957.7 WDrop/Amp High
2 AWG33.62 mm²115 A26.88 V (5.6%)453.1 V44.34 V (9.24%)37250.5 WDrop/Amp High
1 AWG42.41 mm²130 A21.31 V (4.44%)458.7 V35.15 V (7.32%)29529.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A16.9 V (3.52%)463.1 V27.87 V (5.81%)23413.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.4 V (2.79%)466.6 V22.11 V (4.61%)18572.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.63 V (2.21%)469.4 V17.54 V (3.65%)14731.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.43 V (1.76%)471.6 V13.91 V (2.9%)11682.5 WDrop/Amp High
250 kcmil126.7 mm²255 A7.13 V (1.49%)472.9 V11.77 V (2.45%)9884.5 WDrop/Amp High
300 kcmil152.0 mm²285 A5.95 V (1.24%)474.1 V9.81 V (2.04%)8239.2 WDrop/Amp High
350 kcmil177.3 mm²310 A5.1 V (1.06%)474.9 V8.41 V (1.75%)7063.5 WDrop/Amp High
400 kcmil202.7 mm²335 A4.46 V (0.93%)475.5 V7.36 V (1.53%)6178.4 WDrop/Amp High
500 kcmil253.4 mm²380 A3.57 V (0.74%)476.4 V5.88 V (1.23%)4942.2 WDrop/Amp High
600 kcmil304.0 mm²420 A2.97 V (0.62%)477.0 V4.9 V (1.02%)4119.6 WDrop/Amp High
750 kcmil380.0 mm²475 A2.38 V (0.5%)477.6 V3.92 V (0.82%)3295.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.78 V (0.37%)478.2 V2.94 V (0.61%)2471.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 100 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 100 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.89V (0.18%) and delivers 479.1V at the load.

What size aluminum wire is required for 800 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.94V (0.61%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.