🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 120 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.23%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.53V (0.74%)
Voltage at Load End478.9 VLoss: 1.07 V (1483.0 W)
Power & Breaker (125%)665.11 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 120 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A521.43 V (108.63%)0.0 V860.12 V (179.19%)722516.7 WDrop/Amp High
12 AWG3.31 mm²20 A327.67 V (68.26%)152.3 V540.5 V (112.6%)454028.6 WDrop/Amp High
10 AWG5.26 mm²30 A206.19 V (42.96%)273.8 V340.12 V (70.86%)285710.0 WDrop/Amp High
8 AWG8.37 mm²50 A129.58 V (27.0%)350.4 V213.75 V (44.53%)179550.1 WDrop/Amp High
6 AWG13.3 mm²65 A81.55 V (16.99%)398.5 V134.51 V (28.02%)112995.1 WDrop/Amp High
4 AWG21.15 mm²85 A51.28 V (10.68%)428.7 V84.59 V (17.62%)71056.0 WDrop/Amp High
3 AWG26.67 mm²100 A40.67 V (8.47%)439.3 V67.08 V (13.98%)56349.3 WDrop/Amp High
2 AWG33.62 mm²115 A32.26 V (6.72%)447.7 V53.21 V (11.09%)44700.6 WDrop/Amp High
1 AWG42.41 mm²130 A25.57 V (5.33%)454.4 V42.18 V (8.79%)35435.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A20.28 V (4.22%)459.7 V33.45 V (6.97%)28095.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A16.08 V (3.35%)463.9 V26.53 V (5.53%)22287.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.76 V (2.66%)467.2 V21.05 V (4.38%)17678.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.12 V (2.11%)469.9 V16.69 V (3.48%)14019.0 WDrop/Amp High
250 kcmil126.7 mm²255 A8.56 V (1.78%)471.4 V14.12 V (2.94%)11861.4 WDrop/Amp High
300 kcmil152.0 mm²285 A7.14 V (1.49%)472.9 V11.77 V (2.45%)9887.1 WDrop/Amp High
350 kcmil177.3 mm²310 A6.12 V (1.27%)473.9 V10.09 V (2.1%)8476.2 WDrop/Amp High
400 kcmil202.7 mm²335 A5.35 V (1.11%)474.6 V8.83 V (1.84%)7414.1 WDrop/Amp High
500 kcmil253.4 mm²380 A4.28 V (0.89%)475.7 V7.06 V (1.47%)5930.7 WDrop/Amp High
600 kcmil304.0 mm²420 A3.57 V (0.74%)476.4 V5.89 V (1.23%)4943.5 WDrop/Amp High
750 kcmil380.0 mm²475 A2.85 V (0.59%)477.1 V4.71 V (0.98%)3954.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.14 V (0.45%)477.9 V3.53 V (0.74%)2965.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 120 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 120 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.07V (0.23%) and delivers 478.9V at the load.

What size aluminum wire is required for 800 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.53V (0.74%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.