🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 80 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.15%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.35V (0.49%)
Voltage at Load End479.3 VLoss: 0.71 V (988.6 W)
Power & Breaker (125%)665.11 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 80 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A347.62 V (72.42%)132.4 V573.41 V (119.46%)481677.8 WDrop/Amp High
12 AWG3.31 mm²20 A218.44 V (45.51%)261.6 V360.33 V (75.07%)302685.7 WDrop/Amp High
10 AWG5.26 mm²30 A137.46 V (28.64%)342.5 V226.75 V (47.24%)190473.3 WDrop/Amp High
8 AWG8.37 mm²50 A86.39 V (18.0%)393.6 V142.5 V (29.69%)119700.1 WDrop/Amp High
6 AWG13.3 mm²65 A54.36 V (11.33%)425.6 V89.68 V (18.68%)75330.1 WDrop/Amp High
4 AWG21.15 mm²85 A34.19 V (7.12%)445.8 V56.39 V (11.75%)47370.7 WDrop/Amp High
3 AWG26.67 mm²100 A27.11 V (5.65%)452.9 V44.72 V (9.32%)37566.2 WDrop/Amp High
2 AWG33.62 mm²115 A21.51 V (4.48%)458.5 V35.48 V (7.39%)29800.4 WDrop/Amp High
1 AWG42.41 mm²130 A17.05 V (3.55%)463.0 V28.12 V (5.86%)23623.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.52 V (2.82%)466.5 V22.3 V (4.65%)18730.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.72 V (2.23%)469.3 V17.69 V (3.68%)14858.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.51 V (1.77%)471.5 V14.03 V (2.92%)11785.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.74 V (1.41%)473.3 V11.13 V (2.32%)9346.0 WDrop/Amp High
250 kcmil126.7 mm²255 A5.71 V (1.19%)474.3 V9.41 V (1.96%)7907.6 WDrop/Amp High
300 kcmil152.0 mm²285 A4.76 V (0.99%)475.2 V7.85 V (1.63%)6591.4 WDrop/Amp High
350 kcmil177.3 mm²310 A4.08 V (0.85%)475.9 V6.73 V (1.4%)5650.8 WDrop/Amp High
400 kcmil202.7 mm²335 A3.57 V (0.74%)476.4 V5.88 V (1.23%)4942.7 WDrop/Amp High
500 kcmil253.4 mm²380 A2.85 V (0.59%)477.1 V4.71 V (0.98%)3953.8 WDrop/Amp High
600 kcmil304.0 mm²420 A2.38 V (0.5%)477.6 V3.92 V (0.82%)3295.7 WDrop/Amp High
750 kcmil380.0 mm²475 A1.9 V (0.4%)478.1 V3.14 V (0.65%)2636.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.43 V (0.3%)478.6 V2.35 V (0.49%)1977.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 80 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 80 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.71V (0.15%) and delivers 479.3V at the load.

What size aluminum wire is required for 800 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.35V (0.49%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.