🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 40 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.07%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.18V (0.25%)
Voltage at Load End479.6 VLoss: 0.35 V (494.3 W)
Power & Breaker (125%)665.11 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 40 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A173.81 V (36.21%)306.2 V286.71 V (59.73%)240838.9 WDrop/Amp High
12 AWG3.31 mm²20 A109.22 V (22.75%)370.8 V180.17 V (37.53%)151342.9 WDrop/Amp High
10 AWG5.26 mm²30 A68.73 V (14.32%)411.3 V113.37 V (23.62%)95236.7 WDrop/Amp High
8 AWG8.37 mm²50 A43.19 V (9.0%)436.8 V71.25 V (14.84%)59850.0 WDrop/Amp High
6 AWG13.3 mm²65 A27.18 V (5.66%)452.8 V44.84 V (9.34%)37665.0 WDrop/Amp High
4 AWG21.15 mm²85 A17.09 V (3.56%)462.9 V28.2 V (5.87%)23685.3 WDrop/Amp High
3 AWG26.67 mm²100 A13.56 V (2.82%)466.4 V22.36 V (4.66%)18783.1 WDrop/Amp High
2 AWG33.62 mm²115 A10.75 V (2.24%)469.2 V17.74 V (3.7%)14900.2 WDrop/Amp High
1 AWG42.41 mm²130 A8.52 V (1.78%)471.5 V14.06 V (2.93%)11812.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.76 V (1.41%)473.2 V11.15 V (2.32%)9365.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.36 V (1.12%)474.6 V8.84 V (1.84%)7429.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.25 V (0.89%)475.7 V7.02 V (1.46%)5892.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.37 V (0.7%)476.6 V5.56 V (1.16%)4673.0 WDrop/Amp High
250 kcmil126.7 mm²255 A2.85 V (0.59%)477.1 V4.71 V (0.98%)3953.8 WDrop/Amp High
300 kcmil152.0 mm²285 A2.38 V (0.5%)477.6 V3.92 V (0.82%)3295.7 WDrop/Amp High
350 kcmil177.3 mm²310 A2.04 V (0.42%)478.0 V3.36 V (0.7%)2825.4 WDrop/Amp High
400 kcmil202.7 mm²335 A1.78 V (0.37%)478.2 V2.94 V (0.61%)2471.4 WDrop/Amp High
500 kcmil253.4 mm²380 A1.43 V (0.3%)478.6 V2.35 V (0.49%)1976.9 WDrop/Amp High
600 kcmil304.0 mm²420 A1.19 V (0.25%)478.8 V1.96 V (0.41%)1647.8 WDrop/Amp High
750 kcmil380.0 mm²475 A0.95 V (0.2%)479.0 V1.57 V (0.33%)1318.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.71 V (0.15%)479.3 V1.18 V (0.25%)988.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 40 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 40 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (0.07%) and delivers 479.6V at the load.

What size aluminum wire is required for 800 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.18V (0.25%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.