90 Amp Wire Size at 225 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 90 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.59%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 3.44V (2.87%)
Voltage at Load End116.9 VLoss: 3.11 V (279.7 W)
Power & Breaker (125%)10.8 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 90 Amps at 225 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A127.0 V (105.84%)0.0 V209.5 V (174.58%)11430.4 WDrop/Amp High
12 AWG3.31 mm²20 A79.81 V (66.51%)40.2 V131.65 V (109.71%)7182.9 WDrop/Amp High
10 AWG5.26 mm²30 A50.22 V (41.85%)69.8 V82.84 V (69.04%)4520.0 WDrop/Amp High
8 AWG8.37 mm²50 A31.56 V (26.3%)88.4 V52.06 V (43.38%)2840.5 WDrop/Amp High
6 AWG13.3 mm²65 A19.86 V (16.55%)100.1 V32.76 V (27.3%)1787.6 WDrop/Amp High
4 AWG21.15 mm²85 A12.49 V (10.41%)107.5 V20.6 V (17.17%)1124.1 WDrop/Amp High
3 AWG26.67 mm²100 A9.91 V (8.25%)110.1 V16.34 V (13.62%)891.5 WDrop/Amp High
2 AWG33.62 mm²115 A7.86 V (6.55%)112.1 V12.96 V (10.8%)707.2 WDrop/Amp High
1 AWG42.41 mm²130 A6.23 V (5.19%)113.8 V10.27 V (8.56%)560.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.94 V (4.12%)115.1 V8.15 V (6.79%)444.5 W~ ≤5%
2/0 AWG67.43 mm²175 A3.92 V (3.26%)116.1 V6.46 V (5.39%)352.6 W~ ≤5%
3/0 AWG85.01 mm²200 A3.11 V (2.59%)116.9 V5.13 V (4.27%)279.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.46 V (2.05%)117.5 V4.06 V (3.39%)221.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.09 V (1.74%)117.9 V3.44 V (2.87%)187.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.74 V (1.45%)118.3 V2.87 V (2.39%)156.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.49 V (1.24%)118.5 V2.46 V (2.05%)134.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.3 V (1.09%)118.7 V2.15 V (1.79%)117.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.04 V (0.87%)119.0 V1.72 V (1.43%)93.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.87 V (0.72%)119.1 V1.43 V (1.19%)78.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.7 V (0.58%)119.3 V1.15 V (0.96%)62.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.52 V (0.43%)119.5 V0.86 V (0.72%)46.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 90 amps at 225 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 90A load over 225 feet one-way at 120V (1-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 3.11V (2.59%) and delivers 116.9V at the load.

What size aluminum wire is required for 90 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 3.44V (2.87%).

What breaker size is needed for a 90A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (90A × 1.25 = 112.5A), which corresponds to a standard 125A circuit breaker.