⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

90 Amp Wire Size at 225 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 90 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 1.79%
Aluminum Wire (≤3% Drop)2 AWGDrop: 11.22V (2.34%)
Voltage at Load End471.4 VLoss: 8.58 V (1337.2 W)
Power & Breaker (125%)74.82 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 90 Amps at 225 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A109.99 V (22.91%)370.0 V181.43 V (37.8%)17145.7 WDrop/Amp High
12 AWG3.31 mm²20 A69.12 V (14.4%)410.9 V114.01 V (23.75%)10774.3 WDrop/Amp High
10 AWG5.26 mm²30 A43.49 V (9.06%)436.5 V71.74 V (14.95%)6780.0 WDrop/Amp High
8 AWG8.37 mm²50 A27.33 V (5.69%)452.7 V45.09 V (9.39%)4260.8 WDrop/Amp High
6 AWG13.3 mm²65 A17.2 V (3.58%)462.8 V28.37 V (5.91%)2681.4 WDrop/Amp High
4 AWG21.15 mm²85 A10.82 V (2.25%)469.2 V17.84 V (3.72%)1686.2 WDrop/Amp High
3 AWG26.67 mm²100 A8.58 V (1.79%)471.4 V14.15 V (2.95%)1337.2 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A6.8 V (1.42%)473.2 V11.22 V (2.34%)1060.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A5.39 V (1.12%)474.6 V8.9 V (1.85%)840.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A4.28 V (0.89%)475.7 V7.06 V (1.47%)666.7 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.39 V (0.71%)476.6 V5.6 V (1.17%)528.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.69 V (0.56%)477.3 V4.44 V (0.92%)419.5 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.13 V (0.44%)477.9 V3.52 V (0.73%)332.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.81 V (0.38%)478.2 V2.98 V (0.62%)281.5 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.51 V (0.31%)478.5 V2.48 V (0.52%)234.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.29 V (0.27%)478.7 V2.13 V (0.44%)201.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.13 V (0.24%)478.9 V1.86 V (0.39%)175.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.9 V (0.19%)479.1 V1.49 V (0.31%)140.7 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.75 V (0.16%)479.2 V1.24 V (0.26%)117.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.6 V (0.13%)479.4 V0.99 V (0.21%)93.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.45 V (0.09%)479.5 V0.74 V (0.16%)70.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 90 amps at 225 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 90A load over 225 feet one-way at 480V (3-Phase), you need 3 AWG copper wire. This produces a voltage drop of 8.58V (1.79%) and delivers 471.4V at the load.

What size aluminum wire is required for 90 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 11.22V (2.34%).

What breaker size is needed for a 90A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (90A × 1.25 = 112.5A), which corresponds to a standard 125A circuit breaker.