🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 1000 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.41%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 33.1V (15.91%)
Voltage at Load End203.0 VLoss: 5.02 V (7820.3 W)
Power & Breaker (125%)324.24 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 1000 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4888.42 V (2350.2%)0.0 V8063.61 V (3876.74%)7620293.1 WDrop/Amp High
12 AWG3.31 mm²20 A3071.88 V (1476.86%)0.0 V5067.16 V (2436.14%)4788583.0 WDrop/Amp High
10 AWG5.26 mm²30 A1933.06 V (929.36%)0.0 V3188.65 V (1533.01%)3013347.8 WDrop/Amp High
8 AWG8.37 mm²50 A1214.8 V (584.04%)0.0 V2003.86 V (963.39%)1893692.9 WDrop/Amp High
6 AWG13.3 mm²65 A764.5 V (367.55%)0.0 V1261.08 V (606.29%)1191745.1 WDrop/Amp High
4 AWG21.15 mm²85 A480.75 V (231.13%)0.0 V793.02 V (381.26%)749418.9 WDrop/Amp High
3 AWG26.67 mm²100 A381.25 V (183.29%)0.0 V628.88 V (302.35%)594308.6 WDrop/Amp High
2 AWG33.62 mm²115 A302.44 V (145.4%)0.0 V498.88 V (239.85%)471451.8 WDrop/Amp High
1 AWG42.41 mm²130 A239.75 V (115.27%)0.0 V395.48 V (190.13%)373737.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A190.09 V (91.39%)17.9 V313.56 V (150.75%)296321.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A150.79 V (72.5%)57.2 V248.74 V (119.58%)235061.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A119.61 V (57.5%)88.4 V197.3 V (94.85%)186451.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A94.85 V (45.6%)113.2 V156.46 V (75.22%)147856.4 WDrop/Amp High
250 kcmil126.7 mm²255 A80.25 V (38.58%)127.7 V132.38 V (63.64%)125100.3 WDrop/Amp High
300 kcmil152.0 mm²285 A66.89 V (32.16%)141.1 V110.34 V (53.05%)104277.7 WDrop/Amp High
350 kcmil177.3 mm²310 A57.35 V (27.57%)150.7 V94.6 V (45.48%)89397.7 WDrop/Amp High
400 kcmil202.7 mm²335 A50.16 V (24.12%)157.8 V82.74 V (39.78%)78195.4 WDrop/Amp High
500 kcmil253.4 mm²380 A40.13 V (19.29%)167.9 V66.19 V (31.82%)62550.2 WDrop/Amp High
600 kcmil304.0 mm²420 A33.45 V (16.08%)174.6 V55.17 V (26.53%)52138.8 WDrop/Amp High
750 kcmil380.0 mm²475 A26.76 V (12.86%)181.2 V44.14 V (21.22%)41711.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A20.07 V (9.65%)187.9 V33.1 V (15.91%)31281.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 1000 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 1000 feet one-way at 208V (3-Phase), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.02V (2.41%) and delivers 203.0V at the load.

What size aluminum wire is required for 900 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 33.1V (15.91%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.