🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 1000 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 33.1V (13.79%)
Voltage at Load End233.3 VLoss: 6.69 V (10427.1 W)
Power & Breaker (125%)374.12 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 1000 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4888.42 V (2036.84%)0.0 V8063.61 V (3359.84%)7620293.1 WDrop/Amp High
12 AWG3.31 mm²20 A3071.88 V (1279.95%)0.0 V5067.16 V (2111.32%)4788583.0 WDrop/Amp High
10 AWG5.26 mm²30 A1933.06 V (805.44%)0.0 V3188.65 V (1328.6%)3013347.8 WDrop/Amp High
8 AWG8.37 mm²50 A1214.8 V (506.17%)0.0 V2003.86 V (834.94%)1893692.9 WDrop/Amp High
6 AWG13.3 mm²65 A764.5 V (318.54%)0.0 V1261.08 V (525.45%)1191745.1 WDrop/Amp High
4 AWG21.15 mm²85 A480.75 V (200.31%)0.0 V793.02 V (330.42%)749418.9 WDrop/Amp High
3 AWG26.67 mm²100 A381.25 V (158.85%)0.0 V628.88 V (262.03%)594308.6 WDrop/Amp High
2 AWG33.62 mm²115 A302.44 V (126.02%)0.0 V498.88 V (207.87%)471451.8 WDrop/Amp High
1 AWG42.41 mm²130 A239.75 V (99.9%)0.2 V395.48 V (164.78%)373737.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A190.09 V (79.2%)49.9 V313.56 V (130.65%)296321.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A150.79 V (62.83%)89.2 V248.74 V (103.64%)235061.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A119.61 V (49.84%)120.4 V197.3 V (82.21%)186451.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A94.85 V (39.52%)145.2 V156.46 V (65.19%)147856.4 WDrop/Amp High
250 kcmil126.7 mm²255 A80.25 V (33.44%)159.7 V132.38 V (55.16%)125100.3 WDrop/Amp High
300 kcmil152.0 mm²285 A66.89 V (27.87%)173.1 V110.34 V (45.98%)104277.7 WDrop/Amp High
350 kcmil177.3 mm²310 A57.35 V (23.9%)182.7 V94.6 V (39.42%)89397.7 WDrop/Amp High
400 kcmil202.7 mm²335 A50.16 V (20.9%)189.8 V82.74 V (34.48%)78195.4 WDrop/Amp High
500 kcmil253.4 mm²380 A40.13 V (16.72%)199.9 V66.19 V (27.58%)62550.2 WDrop/Amp High
600 kcmil304.0 mm²420 A33.45 V (13.94%)206.6 V55.17 V (22.99%)52138.8 WDrop/Amp High
750 kcmil380.0 mm²475 A26.76 V (11.15%)213.2 V44.14 V (18.39%)41711.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A20.07 V (8.36%)219.9 V33.1 V (13.79%)31281.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 1000 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 1000 feet one-way at 240V (3-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 6.69V (2.79%) and delivers 233.3V at the load.

What size aluminum wire is required for 900 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 33.1V (13.79%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.