900 Amp Wire Size at 250 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.21%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.56V (3.98%)
Voltage at Load End237.1 VLoss: 2.9 V (2606.8 W)
Power & Breaker (125%)216.0 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 250 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1411.17 V (587.99%)0.0 V2327.76 V (969.9%)1270048.8 WDrop/Amp High
12 AWG3.31 mm²20 A886.77 V (369.49%)0.0 V1462.76 V (609.48%)798097.2 WDrop/Amp High
10 AWG5.26 mm²30 A558.03 V (232.51%)0.0 V920.48 V (383.54%)502224.6 WDrop/Amp High
8 AWG8.37 mm²50 A350.68 V (146.12%)0.0 V578.46 V (241.03%)315615.5 WDrop/Amp High
6 AWG13.3 mm²65 A220.69 V (91.96%)19.3 V364.04 V (151.68%)198624.2 WDrop/Amp High
4 AWG21.15 mm²85 A138.78 V (57.83%)101.2 V228.92 V (95.39%)124903.1 WDrop/Amp High
3 AWG26.67 mm²100 A110.06 V (45.86%)129.9 V181.54 V (75.64%)99051.4 WDrop/Amp High
2 AWG33.62 mm²115 A87.31 V (36.38%)152.7 V144.01 V (60.01%)78575.3 WDrop/Amp High
1 AWG42.41 mm²130 A69.21 V (28.84%)170.8 V114.17 V (47.57%)62289.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A54.87 V (22.86%)185.1 V90.52 V (37.72%)49386.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A43.53 V (18.14%)196.5 V71.8 V (29.92%)39176.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A34.53 V (14.39%)205.5 V56.96 V (23.73%)31075.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A27.38 V (11.41%)212.6 V45.17 V (18.82%)24642.7 WDrop/Amp High
250 kcmil126.7 mm²255 A23.17 V (9.65%)216.8 V38.21 V (15.92%)20850.1 WDrop/Amp High
300 kcmil152.0 mm²285 A19.31 V (8.05%)220.7 V31.85 V (13.27%)17379.6 WDrop/Amp High
350 kcmil177.3 mm²310 A16.56 V (6.9%)223.4 V27.31 V (11.38%)14899.6 WDrop/Amp High
400 kcmil202.7 mm²335 A14.48 V (6.03%)225.5 V23.89 V (9.95%)13032.6 WDrop/Amp High
500 kcmil253.4 mm²380 A11.58 V (4.83%)228.4 V19.11 V (7.96%)10425.0 WDrop/Amp High
600 kcmil304.0 mm²420 A9.66 V (4.02%)230.3 V15.93 V (6.64%)8689.8 WDrop/Amp High
750 kcmil380.0 mm²475 A7.72 V (3.22%)232.3 V12.74 V (5.31%)6951.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.79 V (2.41%)234.2 V9.56 V (3.98%)5213.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 250 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 250 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.9V (1.21%) and delivers 237.1V at the load.

What size aluminum wire is required for 900 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.56V (3.98%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.