🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 600 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.9%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 22.93V (9.56%)
Voltage at Load End233.1 VLoss: 6.95 V (6256.2 W)
Power & Breaker (125%)216.0 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3386.8 V (1411.17%)0.0 V5586.63 V (2327.76%)3048117.2 WDrop/Amp High
12 AWG3.31 mm²20 A2128.26 V (886.77%)0.0 V3510.63 V (1462.76%)1915433.2 WDrop/Amp High
10 AWG5.26 mm²30 A1339.27 V (558.03%)0.0 V2209.16 V (920.48%)1205339.1 WDrop/Amp High
8 AWG8.37 mm²50 A841.64 V (350.68%)0.0 V1388.31 V (578.46%)757477.2 WDrop/Amp High
6 AWG13.3 mm²65 A529.66 V (220.69%)0.0 V873.7 V (364.04%)476698.0 WDrop/Amp High
4 AWG21.15 mm²85 A333.08 V (138.78%)0.0 V549.42 V (228.92%)299767.6 WDrop/Amp High
3 AWG26.67 mm²100 A264.14 V (110.06%)0.0 V435.7 V (181.54%)237723.4 WDrop/Amp High
2 AWG33.62 mm²115 A209.53 V (87.31%)30.5 V345.63 V (144.01%)188580.7 WDrop/Amp High
1 AWG42.41 mm²130 A166.11 V (69.21%)73.9 V274.0 V (114.17%)149495.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A131.7 V (54.87%)108.3 V217.24 V (90.52%)118528.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A104.47 V (43.53%)135.5 V172.33 V (71.8%)94024.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A82.87 V (34.53%)157.1 V136.69 V (56.96%)74580.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A65.71 V (27.38%)174.3 V108.4 V (45.17%)59142.6 WDrop/Amp High
250 kcmil126.7 mm²255 A55.6 V (23.17%)184.4 V91.71 V (38.21%)50040.1 WDrop/Amp High
300 kcmil152.0 mm²285 A46.35 V (19.31%)193.7 V76.45 V (31.85%)41711.1 WDrop/Amp High
350 kcmil177.3 mm²310 A39.73 V (16.56%)200.3 V65.54 V (27.31%)35759.1 WDrop/Amp High
400 kcmil202.7 mm²335 A34.75 V (14.48%)205.2 V57.33 V (23.89%)31278.2 WDrop/Amp High
500 kcmil253.4 mm²380 A27.8 V (11.58%)212.2 V45.86 V (19.11%)25020.1 WDrop/Amp High
600 kcmil304.0 mm²420 A23.17 V (9.66%)216.8 V38.22 V (15.93%)20855.5 WDrop/Amp High
750 kcmil380.0 mm²475 A18.54 V (7.72%)221.5 V30.58 V (12.74%)16684.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A13.9 V (5.79%)226.1 V22.93 V (9.56%)12512.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 600 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 6.95V (2.9%) and delivers 233.1V at the load.

What size aluminum wire is required for 900 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 22.93V (9.56%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.