⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 750 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)5× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.9%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 28.67V (23.89%)
Voltage at Load End116.5 VLoss: 3.48 V (3128.1 W)
Power & Breaker (125%)108.0 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 750 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4233.5 V (3527.91%)0.0 V6983.29 V (5819.41%)3810146.5 WDrop/Amp High
12 AWG3.31 mm²20 A2660.32 V (2216.94%)0.0 V4388.29 V (3656.91%)2394291.5 WDrop/Amp High
10 AWG5.26 mm²30 A1674.08 V (1395.07%)0.0 V2761.45 V (2301.21%)1506673.9 WDrop/Amp High
8 AWG8.37 mm²50 A1052.05 V (876.71%)0.0 V1735.39 V (1446.16%)946846.5 WDrop/Amp High
6 AWG13.3 mm²65 A662.08 V (551.73%)0.0 V1092.12 V (910.1%)595872.5 WDrop/Amp High
4 AWG21.15 mm²85 A416.34 V (346.95%)0.0 V686.77 V (572.31%)374709.4 WDrop/Amp High
3 AWG26.67 mm²100 A330.17 V (275.14%)0.0 V544.63 V (453.86%)297154.3 WDrop/Amp High
2 AWG33.62 mm²115 A261.92 V (218.26%)0.0 V432.04 V (360.03%)235725.9 WDrop/Amp High
1 AWG42.41 mm²130 A207.63 V (173.03%)0.0 V342.5 V (285.41%)186868.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A164.62 V (137.19%)0.0 V271.55 V (226.29%)148160.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A130.59 V (108.82%)0.0 V215.41 V (179.51%)117530.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A103.58 V (86.32%)16.4 V170.87 V (142.39%)93225.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A82.14 V (68.45%)37.9 V135.5 V (112.91%)73928.2 WDrop/Amp High
250 kcmil126.7 mm²255 A69.5 V (57.92%)50.5 V114.64 V (95.54%)62550.2 WDrop/Amp High
300 kcmil152.0 mm²285 A57.93 V (48.28%)62.1 V95.56 V (79.63%)52138.8 WDrop/Amp High
350 kcmil177.3 mm²310 A49.67 V (41.39%)70.3 V81.92 V (68.27%)44698.8 WDrop/Amp High
400 kcmil202.7 mm²335 A43.44 V (36.2%)76.6 V71.66 V (59.72%)39097.7 WDrop/Amp High
500 kcmil253.4 mm²380 A34.75 V (28.96%)85.2 V57.32 V (47.77%)31275.1 WDrop/Amp High
600 kcmil304.0 mm²420 A28.97 V (24.14%)91.0 V47.78 V (39.82%)26069.4 WDrop/Amp High
750 kcmil380.0 mm²475 A23.17 V (19.31%)96.8 V38.22 V (31.85%)20855.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A17.38 V (14.48%)102.6 V28.67 V (23.89%)15640.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 750 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 750 feet one-way at 120V (1-Phase), you need 5× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.48V (2.9%) and delivers 116.5V at the load.

What size aluminum wire is required for 900 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 28.67V (23.89%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.