225 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 225 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 16.68V (2.42%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 20.64V (2.99%)
Voltage at Load673.3 VLine Loss: 6500.2 W
Max Power & Breaker268.9 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3335.93 V (483.47%)0.0 V5502.73 V (797.5%)1300050.0 WDrop High
2.5 mm²24 A18 A2001.56 V (290.08%)0.0 V3301.64 V (478.5%)780030.0 WDrop High
4 mm²32 A25 A1250.97 V (181.3%)0.0 V2063.52 V (299.06%)487518.8 WDrop High
6 mm²41 A32 A833.98 V (120.87%)0.0 V1375.68 V (199.37%)325012.5 WDrop High
10 mm²57 A44 A500.39 V (72.52%)189.6 V825.41 V (119.62%)195007.5 WDrop High
16 mm²76 A59 A312.74 V (45.33%)377.3 V515.88 V (74.77%)121879.7 WDrop High
25 mm²101 A78 A200.16 V (29.01%)489.8 V330.16 V (47.85%)78003.0 WDrop High
35 mm²125 A97 A142.97 V (20.72%)547.0 V235.83 V (34.18%)55716.4 WDrop High
50 mm²151 A118 A100.08 V (14.5%)589.9 V165.08 V (23.92%)39001.5 WDrop High
70 mm²192 A150 A71.48 V (10.36%)618.5 V117.92 V (17.09%)27858.2 WDrop High
95 mm²232 A181 A52.67 V (7.63%)637.3 V86.89 V (12.59%)20527.1 WDrop High
120 mm²269 A210 A41.7 V (6.04%)648.3 V68.78 V (9.97%)16250.6 WDrop High
150 mm²309 A241 A33.36 V (4.83%)656.6 V55.03 V (7.97%)13000.5 W~ ≤5%
185 mm²353 A275 A27.05 V (3.92%)663.0 V44.62 V (6.47%)10540.9 W~ ≤5%
240 mm²415 A324 A20.85 V (3.02%)669.2 V34.39 V (4.98%)8125.3 W~ ≤5%
300 mm²477 A372 A16.68 V (2.42%)673.3 V27.51 V (3.99%)6500.2 W✓ OK (≤3%)
400 mm²570 A445 A12.51 V (1.81%)677.5 V20.64 V (2.99%)4875.2 W✓ OK (≤3%)

FAQ — 225 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 225A at 600 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 225A over 600m at 690V (voltage drop: 16.68V or 2.42%).

What is the power capacity of 225A at 690V?

At unity power factor, 225A at 690V supports 268.9 kW with a standard 225A circuit breaker.