30 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 30 A over 80 m (262.5 ft).
Copper Cable (≤3% Drop)95 mm²Drop: 1.08V (2.25%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 1.41V (2.94%)
Voltage at Load46.9 VLine Loss: 32.4 W
Max Power & Breaker1.44 kW30A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 80m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 68.48 V (142.67%) | 0.0 V | 112.96 V (235.33%) | 2054.4 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 41.09 V (85.6%) | 6.9 V | 67.78 V (141.2%) | 1232.6 W | Drop High |
| 4 mm² | 32 A | 25 A | 25.68 V (53.5%) | 22.3 V | 42.36 V (88.25%) | 770.4 W | Drop High |
| 6 mm² | 41 A | 32 A | 17.12 V (35.67%) | 30.9 V | 28.24 V (58.83%) | 513.6 W | Drop High |
| 10 mm² | 57 A | 44 A | 10.27 V (21.4%) | 37.7 V | 16.94 V (35.3%) | 308.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 6.42 V (13.38%) | 41.6 V | 10.59 V (22.06%) | 192.6 W | Drop High |
| 25 mm² | 101 A | 78 A | 4.11 V (8.56%) | 43.9 V | 6.78 V (14.12%) | 123.3 W | Drop High |
| 35 mm² | 125 A | 97 A | 2.93 V (6.11%) | 45.1 V | 4.84 V (10.09%) | 88.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 2.05 V (4.28%) | 45.9 V | 3.39 V (7.06%) | 61.6 W | ~ ≤5% |
| 70 mm² | 192 A | 150 A | 1.47 V (3.06%) | 46.5 V | 2.42 V (5.04%) | 44.0 W | ~ ≤5% |
| 95 mm² | 232 A | 181 A | 1.08 V (2.25%) | 46.9 V | 1.78 V (3.72%) | 32.4 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.86 V (1.78%) | 47.1 V | 1.41 V (2.94%) | 25.7 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.68 V (1.43%) | 47.3 V | 1.13 V (2.35%) | 20.5 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.56 V (1.16%) | 47.4 V | 0.92 V (1.91%) | 16.7 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.43 V (0.89%) | 47.6 V | 0.71 V (1.47%) | 12.8 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.34 V (0.71%) | 47.7 V | 0.56 V (1.18%) | 10.3 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.26 V (0.53%) | 47.7 V | 0.42 V (0.88%) | 7.7 W | ✓ OK (≤3%) |
FAQ — 30 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))
What mm² cable size is required for 30A at 80 meters (48V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 95 mm² copper cable for 30A over 80m at 48V (voltage drop: 1.08V or 2.25%).
What is the power capacity of 30A at 48V?
At unity power factor, 30A at 48V supports 1.44 kW with a standard 30A circuit breaker.
Related Lengths & Currents (48V)
30A · 5m (48V)30A · 10m (48V)30A · 15m (48V)30A · 20m (48V)30A · 25m (48V)30A · 30m (48V)30A · 35m (48V)30A · 40m (48V)30A · 45m (48V)30A · 50m (48V)30A · 60m (48V)30A · 70m (48V)10A · 80m (48V)16A · 80m (48V)20A · 80m (48V)25A · 80m (48V)32A · 80m (48V)40A · 80m (48V)50A · 80m (48V)63A · 80m (48V)80A · 80m (48V)100A · 80m (48V)125A · 80m (48V)160A · 80m (48V)200A · 80m (48V)