300 Amp Cable Size at 100 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 300 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 7.41V (1.07%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 7.64V (1.11%)
Voltage at Load682.6 VLine Loss: 3852.0 W
Max Power & Breaker358.53 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A741.32 V (107.44%)0.0 V1222.83 V (177.22%)385200.0 WDrop High
2.5 mm²24 A18 A444.79 V (64.46%)245.2 V733.7 V (106.33%)231120.0 WDrop High
4 mm²32 A25 A277.99 V (40.29%)412.0 V458.56 V (66.46%)144450.0 WDrop High
6 mm²41 A32 A185.33 V (26.86%)504.7 V305.71 V (44.31%)96300.0 WDrop High
10 mm²57 A44 A111.2 V (16.12%)578.8 V183.42 V (26.58%)57780.0 WDrop High
16 mm²76 A59 A69.5 V (10.07%)620.5 V114.64 V (16.61%)36112.5 WDrop High
25 mm²101 A78 A44.48 V (6.45%)645.5 V73.37 V (10.63%)23112.0 WDrop High
35 mm²125 A97 A31.77 V (4.6%)658.2 V52.41 V (7.6%)16508.6 WDrop High
50 mm²151 A118 A22.24 V (3.22%)667.8 V36.68 V (5.32%)11556.0 WDrop High
70 mm²192 A150 A15.89 V (2.3%)674.1 V26.2 V (3.8%)8254.3 WDrop High
95 mm²232 A181 A11.71 V (1.7%)678.3 V19.31 V (2.8%)6082.1 WDrop High
120 mm²269 A210 A9.27 V (1.34%)680.7 V15.29 V (2.22%)4815.0 WDrop High
150 mm²309 A241 A7.41 V (1.07%)682.6 V12.23 V (1.77%)3852.0 W✓ OK (≤3%)
185 mm²353 A275 A6.01 V (0.87%)684.0 V9.91 V (1.44%)3123.2 W✓ OK (≤3%)
240 mm²415 A324 A4.63 V (0.67%)685.4 V7.64 V (1.11%)2407.5 W✓ OK (≤3%)
300 mm²477 A372 A3.71 V (0.54%)686.3 V6.11 V (0.89%)1926.0 W✓ OK (≤3%)
400 mm²570 A445 A2.78 V (0.4%)687.2 V4.59 V (0.66%)1444.5 W✓ OK (≤3%)

FAQ — 300 Amp Cable Size at 100 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 300A at 100 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 300A over 100m at 690V (voltage drop: 7.41V or 1.07%).

What is the power capacity of 300A at 690V?

At unity power factor, 300A at 690V supports 358.53 kW with a standard 300A circuit breaker.