300 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 300 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 0.37V (0.05%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 0.38V (0.06%)
Voltage at Load689.6 VLine Loss: 192.6 W
Max Power & Breaker358.53 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A37.07 V (5.37%)652.9 V61.14 V (8.86%)19260.0 WDrop High
2.5 mm²24 A18 A22.24 V (3.22%)667.8 V36.68 V (5.32%)11556.0 WDrop High
4 mm²32 A25 A13.9 V (2.01%)676.1 V22.93 V (3.32%)7222.5 WDrop High
6 mm²41 A32 A9.27 V (1.34%)680.7 V15.29 V (2.22%)4815.0 WDrop High
10 mm²57 A44 A5.56 V (0.81%)684.4 V9.17 V (1.33%)2889.0 WDrop High
16 mm²76 A59 A3.47 V (0.5%)686.5 V5.73 V (0.83%)1805.6 WDrop High
25 mm²101 A78 A2.22 V (0.32%)687.8 V3.67 V (0.53%)1155.6 WDrop High
35 mm²125 A97 A1.59 V (0.23%)688.4 V2.62 V (0.38%)825.4 WDrop High
50 mm²151 A118 A1.11 V (0.16%)688.9 V1.83 V (0.27%)577.8 WDrop High
70 mm²192 A150 A0.79 V (0.12%)689.2 V1.31 V (0.19%)412.7 WDrop High
95 mm²232 A181 A0.59 V (0.08%)689.4 V0.97 V (0.14%)304.1 WDrop High
120 mm²269 A210 A0.46 V (0.07%)689.5 V0.76 V (0.11%)240.8 WDrop High
150 mm²309 A241 A0.37 V (0.05%)689.6 V0.61 V (0.09%)192.6 W✓ OK (≤3%)
185 mm²353 A275 A0.3 V (0.04%)689.7 V0.5 V (0.07%)156.2 W✓ OK (≤3%)
240 mm²415 A324 A0.23 V (0.03%)689.8 V0.38 V (0.06%)120.4 W✓ OK (≤3%)
300 mm²477 A372 A0.19 V (0.03%)689.8 V0.31 V (0.04%)96.3 W✓ OK (≤3%)
400 mm²570 A445 A0.14 V (0.02%)689.9 V0.23 V (0.03%)72.2 W✓ OK (≤3%)

FAQ — 300 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 300A at 5 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 300A over 5m at 690V (voltage drop: 0.37V or 0.05%).

What is the power capacity of 300A at 690V?

At unity power factor, 300A at 690V supports 358.53 kW with a standard 300A circuit breaker.