300 Amp Cable Size at 20 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 300 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 1.48V (0.21%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 1.53V (0.22%)
Voltage at Load688.5 VLine Loss: 770.4 W
Max Power & Breaker358.53 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A148.26 V (21.49%)541.7 V244.57 V (35.44%)77040.0 WDrop High
2.5 mm²24 A18 A88.96 V (12.89%)601.0 V146.74 V (21.27%)46224.0 WDrop High
4 mm²32 A25 A55.6 V (8.06%)634.4 V91.71 V (13.29%)28890.0 WDrop High
6 mm²41 A32 A37.07 V (5.37%)652.9 V61.14 V (8.86%)19260.0 WDrop High
10 mm²57 A44 A22.24 V (3.22%)667.8 V36.68 V (5.32%)11556.0 WDrop High
16 mm²76 A59 A13.9 V (2.01%)676.1 V22.93 V (3.32%)7222.5 WDrop High
25 mm²101 A78 A8.9 V (1.29%)681.1 V14.67 V (2.13%)4622.4 WDrop High
35 mm²125 A97 A6.35 V (0.92%)683.6 V10.48 V (1.52%)3301.7 WDrop High
50 mm²151 A118 A4.45 V (0.64%)685.6 V7.34 V (1.06%)2311.2 WDrop High
70 mm²192 A150 A3.18 V (0.46%)686.8 V5.24 V (0.76%)1650.9 WDrop High
95 mm²232 A181 A2.34 V (0.34%)687.7 V3.86 V (0.56%)1216.4 WDrop High
120 mm²269 A210 A1.85 V (0.27%)688.1 V3.06 V (0.44%)963.0 WDrop High
150 mm²309 A241 A1.48 V (0.21%)688.5 V2.45 V (0.35%)770.4 W✓ OK (≤3%)
185 mm²353 A275 A1.2 V (0.17%)688.8 V1.98 V (0.29%)624.6 W✓ OK (≤3%)
240 mm²415 A324 A0.93 V (0.13%)689.1 V1.53 V (0.22%)481.5 W✓ OK (≤3%)
300 mm²477 A372 A0.74 V (0.11%)689.3 V1.22 V (0.18%)385.2 W✓ OK (≤3%)
400 mm²570 A445 A0.56 V (0.08%)689.4 V0.92 V (0.13%)288.9 W✓ OK (≤3%)

FAQ — 300 Amp Cable Size at 20 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 300A at 20 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 300A over 20m at 690V (voltage drop: 1.48V or 0.21%).

What is the power capacity of 300A at 690V?

At unity power factor, 300A at 690V supports 358.53 kW with a standard 300A circuit breaker.