⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

300 Amp Cable Size at 40 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 300 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 2.97V (0.43%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 3.06V (0.44%)
Voltage at Load687.0 VLine Loss: 1540.8 W
Max Power & Breaker358.53 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A296.53 V (42.97%)393.5 V489.13 V (70.89%)154080.0 WDrop High
2.5 mm²24 A18 A177.92 V (25.78%)512.1 V293.48 V (42.53%)92448.0 WDrop High
4 mm²32 A25 A111.2 V (16.12%)578.8 V183.42 V (26.58%)57780.0 WDrop High
6 mm²41 A32 A74.13 V (10.74%)615.9 V122.28 V (17.72%)38520.0 WDrop High
10 mm²57 A44 A44.48 V (6.45%)645.5 V73.37 V (10.63%)23112.0 WDrop High
16 mm²76 A59 A27.8 V (4.03%)662.2 V45.86 V (6.65%)14445.0 WDrop High
25 mm²101 A78 A17.79 V (2.58%)672.2 V29.35 V (4.25%)9244.8 WDrop High
35 mm²125 A97 A12.71 V (1.84%)677.3 V20.96 V (3.04%)6603.4 WDrop High
50 mm²151 A118 A8.9 V (1.29%)681.1 V14.67 V (2.13%)4622.4 WDrop High
70 mm²192 A150 A6.35 V (0.92%)683.6 V10.48 V (1.52%)3301.7 WDrop High
95 mm²232 A181 A4.68 V (0.68%)685.3 V7.72 V (1.12%)2432.8 WDrop High
120 mm²269 A210 A3.71 V (0.54%)686.3 V6.11 V (0.89%)1926.0 WDrop High
150 mm²309 A241 A2.97 V (0.43%)687.0 V4.89 V (0.71%)1540.8 W✓ OK (≤3%)
185 mm²353 A275 A2.4 V (0.35%)687.6 V3.97 V (0.57%)1249.3 W✓ OK (≤3%)
240 mm²415 A324 A1.85 V (0.27%)688.1 V3.06 V (0.44%)963.0 W✓ OK (≤3%)
300 mm²477 A372 A1.48 V (0.21%)688.5 V2.45 V (0.35%)770.4 W✓ OK (≤3%)
400 mm²570 A445 A1.11 V (0.16%)688.9 V1.83 V (0.27%)577.8 W✓ OK (≤3%)

FAQ — 300 Amp Cable Size at 40 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 300A at 40 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 300A over 40m at 690V (voltage drop: 2.97V or 0.43%).

What is the power capacity of 300A at 690V?

At unity power factor, 300A at 690V supports 358.53 kW with a standard 300A circuit breaker.