300 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 300 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 1.11V (0.16%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 1.15V (0.17%)
Voltage at Load688.9 VLine Loss: 577.8 W
Max Power & Breaker358.53 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A111.2 V (16.12%)578.8 V183.42 V (26.58%)57780.0 WDrop High
2.5 mm²24 A18 A66.72 V (9.67%)623.3 V110.05 V (15.95%)34668.0 WDrop High
4 mm²32 A25 A41.7 V (6.04%)648.3 V68.78 V (9.97%)21667.5 WDrop High
6 mm²41 A32 A27.8 V (4.03%)662.2 V45.86 V (6.65%)14445.0 WDrop High
10 mm²57 A44 A16.68 V (2.42%)673.3 V27.51 V (3.99%)8667.0 WDrop High
16 mm²76 A59 A10.42 V (1.51%)679.6 V17.2 V (2.49%)5416.9 WDrop High
25 mm²101 A78 A6.67 V (0.97%)683.3 V11.01 V (1.59%)3466.8 WDrop High
35 mm²125 A97 A4.77 V (0.69%)685.2 V7.86 V (1.14%)2476.3 WDrop High
50 mm²151 A118 A3.34 V (0.48%)686.7 V5.5 V (0.8%)1733.4 WDrop High
70 mm²192 A150 A2.38 V (0.35%)687.6 V3.93 V (0.57%)1238.1 WDrop High
95 mm²232 A181 A1.76 V (0.25%)688.2 V2.9 V (0.42%)912.3 WDrop High
120 mm²269 A210 A1.39 V (0.2%)688.6 V2.29 V (0.33%)722.2 WDrop High
150 mm²309 A241 A1.11 V (0.16%)688.9 V1.83 V (0.27%)577.8 W✓ OK (≤3%)
185 mm²353 A275 A0.9 V (0.13%)689.1 V1.49 V (0.22%)468.5 W✓ OK (≤3%)
240 mm²415 A324 A0.69 V (0.1%)689.3 V1.15 V (0.17%)361.1 W✓ OK (≤3%)
300 mm²477 A372 A0.56 V (0.08%)689.4 V0.92 V (0.13%)288.9 W✓ OK (≤3%)
400 mm²570 A445 A0.42 V (0.06%)689.6 V0.69 V (0.1%)216.7 W✓ OK (≤3%)

FAQ — 300 Amp Cable Size at 15 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 300A at 15 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 300A over 15m at 690V (voltage drop: 1.11V or 0.16%).

What is the power capacity of 300A at 690V?

At unity power factor, 300A at 690V supports 358.53 kW with a standard 300A circuit breaker.