⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

300 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 300 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 18.03V (2.61%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 18.34V (2.66%)
Voltage at Load672.0 VLine Loss: 9369.7 W
Max Power & Breaker358.53 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2223.95 V (322.31%)0.0 V3668.48 V (531.66%)1155600.0 WDrop High
2.5 mm²24 A18 A1334.37 V (193.39%)0.0 V2201.09 V (319.0%)693360.0 WDrop High
4 mm²32 A25 A833.98 V (120.87%)0.0 V1375.68 V (199.37%)433350.0 WDrop High
6 mm²41 A32 A555.99 V (80.58%)134.0 V917.12 V (132.92%)288900.0 WDrop High
10 mm²57 A44 A333.59 V (48.35%)356.4 V550.27 V (79.75%)173340.0 WDrop High
16 mm²76 A59 A208.5 V (30.22%)481.5 V343.92 V (49.84%)108337.5 WDrop High
25 mm²101 A78 A133.44 V (19.34%)556.6 V220.11 V (31.9%)69336.0 WDrop High
35 mm²125 A97 A95.31 V (13.81%)594.7 V157.22 V (22.79%)49525.7 WDrop High
50 mm²151 A118 A66.72 V (9.67%)623.3 V110.05 V (15.95%)34668.0 WDrop High
70 mm²192 A150 A47.66 V (6.91%)642.3 V78.61 V (11.39%)24762.9 WDrop High
95 mm²232 A181 A35.12 V (5.09%)654.9 V57.92 V (8.39%)18246.3 WDrop High
120 mm²269 A210 A27.8 V (4.03%)662.2 V45.86 V (6.65%)14445.0 WDrop High
150 mm²309 A241 A22.24 V (3.22%)667.8 V36.68 V (5.32%)11556.0 W~ ≤5%
185 mm²353 A275 A18.03 V (2.61%)672.0 V29.74 V (4.31%)9369.7 W✓ OK (≤3%)
240 mm²415 A324 A13.9 V (2.01%)676.1 V22.93 V (3.32%)7222.5 W✓ OK (≤3%)
300 mm²477 A372 A11.12 V (1.61%)678.9 V18.34 V (2.66%)5778.0 W✓ OK (≤3%)
400 mm²570 A445 A8.34 V (1.21%)681.7 V13.76 V (1.99%)4333.5 W✓ OK (≤3%)

FAQ — 300 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 300A at 300 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 300A over 300m at 690V (voltage drop: 18.03V or 2.61%).

What is the power capacity of 300A at 690V?

At unity power factor, 300A at 690V supports 358.53 kW with a standard 300A circuit breaker.