300 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 300 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 8.34V (2.01%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 27.51V (6.63%)
Voltage at Load406.7 VLine Loss: 4333.5 W
Max Power & Breaker215.64 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4447.91 V (1071.78%)0.0 V7336.97 V (1767.94%)2311200.0 WDrop High
2.5 mm²24 A18 A2668.74 V (643.07%)0.0 V4402.18 V (1060.77%)1386720.0 WDrop High
4 mm²32 A25 A1667.96 V (401.92%)0.0 V2751.36 V (662.98%)866700.0 WDrop High
6 mm²41 A32 A1111.98 V (267.95%)0.0 V1834.24 V (441.99%)577800.0 WDrop High
10 mm²57 A44 A667.19 V (160.77%)0.0 V1100.55 V (265.19%)346680.0 WDrop High
16 mm²76 A59 A416.99 V (100.48%)0.0 V687.84 V (165.74%)216675.0 WDrop High
25 mm²101 A78 A266.87 V (64.31%)148.1 V440.22 V (106.08%)138672.0 WDrop High
35 mm²125 A97 A190.62 V (45.93%)224.4 V314.44 V (75.77%)99051.4 WDrop High
50 mm²151 A118 A133.44 V (32.15%)281.6 V220.11 V (53.04%)69336.0 WDrop High
70 mm²192 A150 A95.31 V (22.97%)319.7 V157.22 V (37.88%)49525.7 WDrop High
95 mm²232 A181 A70.23 V (16.92%)344.8 V115.85 V (27.91%)36492.6 WDrop High
120 mm²269 A210 A55.6 V (13.4%)359.4 V91.71 V (22.1%)28890.0 WDrop High
150 mm²309 A241 A44.48 V (10.72%)370.5 V73.37 V (17.68%)23112.0 WDrop High
185 mm²353 A275 A36.06 V (8.69%)378.9 V59.49 V (14.33%)18739.5 WDrop High
240 mm²415 A324 A27.8 V (6.7%)387.2 V45.86 V (11.05%)14445.0 WDrop High
300 mm²477 A372 A22.24 V (5.36%)392.8 V36.68 V (8.84%)11556.0 WDrop High
400 mm²570 A445 A16.68 V (4.02%)398.3 V27.51 V (6.63%)8667.0 W~ ≤5%

FAQ — 300 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 300A at 600 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 300A over 600m at 415V (voltage drop: 8.34V or 2.01%).

What is the power capacity of 300A at 415V?

At unity power factor, 300A at 415V supports 215.64 kW with a standard 300A circuit breaker.