300 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 300 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)150 mm²Drop: 5.93V (1.43%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 6.11V (1.47%)
Voltage at Load409.1 VLine Loss: 3081.6 W
Max Power & Breaker215.64 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A593.05 V (142.9%)0.0 V978.26 V (235.73%)308160.0 WDrop High
2.5 mm²24 A18 A355.83 V (85.74%)59.2 V586.96 V (141.44%)184896.0 WDrop High
4 mm²32 A25 A222.4 V (53.59%)192.6 V366.85 V (88.4%)115560.0 WDrop High
6 mm²41 A32 A148.26 V (35.73%)266.7 V244.57 V (58.93%)77040.0 WDrop High
10 mm²57 A44 A88.96 V (21.44%)326.0 V146.74 V (35.36%)46224.0 WDrop High
16 mm²76 A59 A55.6 V (13.4%)359.4 V91.71 V (22.1%)28890.0 WDrop High
25 mm²101 A78 A35.58 V (8.57%)379.4 V58.7 V (14.14%)18489.6 WDrop High
35 mm²125 A97 A25.42 V (6.12%)389.6 V41.93 V (10.1%)13206.9 WDrop High
50 mm²151 A118 A17.79 V (4.29%)397.2 V29.35 V (7.07%)9244.8 WDrop High
70 mm²192 A150 A12.71 V (3.06%)402.3 V20.96 V (5.05%)6603.4 WDrop High
95 mm²232 A181 A9.36 V (2.26%)405.6 V15.45 V (3.72%)4865.7 WDrop High
120 mm²269 A210 A7.41 V (1.79%)407.6 V12.23 V (2.95%)3852.0 WDrop High
150 mm²309 A241 A5.93 V (1.43%)409.1 V9.78 V (2.36%)3081.6 W✓ OK (≤3%)
185 mm²353 A275 A4.81 V (1.16%)410.2 V7.93 V (1.91%)2498.6 W✓ OK (≤3%)
240 mm²415 A324 A3.71 V (0.89%)411.3 V6.11 V (1.47%)1926.0 W✓ OK (≤3%)
300 mm²477 A372 A2.97 V (0.71%)412.0 V4.89 V (1.18%)1540.8 W✓ OK (≤3%)
400 mm²570 A445 A2.22 V (0.54%)412.8 V3.67 V (0.88%)1155.6 W✓ OK (≤3%)

FAQ — 300 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 300A at 80 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 150 mm² copper cable for 300A over 80m at 415V (voltage drop: 5.93V or 1.43%).

What is the power capacity of 300A at 415V?

At unity power factor, 300A at 415V supports 215.64 kW with a standard 300A circuit breaker.