325 Amp Cable Size at 120 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 1.39V (2.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.88V (14.34%)
Voltage at Load46.6 VLine Loss: 452.1 W
Max Power & Breaker15.6 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1112.8 V (2318.33%)0.0 V1835.6 V (3824.17%)361660.0 WDrop High
2.5 mm²24 A18 A667.68 V (1391.0%)0.0 V1101.36 V (2294.5%)216996.0 WDrop High
4 mm²32 A25 A417.3 V (869.38%)0.0 V688.35 V (1434.06%)135622.5 WDrop High
6 mm²41 A32 A278.2 V (579.58%)0.0 V458.9 V (956.04%)90415.0 WDrop High
10 mm²57 A44 A166.92 V (347.75%)0.0 V275.34 V (573.62%)54249.0 WDrop High
16 mm²76 A59 A104.33 V (217.34%)0.0 V172.09 V (358.52%)33905.6 WDrop High
25 mm²101 A78 A66.77 V (139.1%)0.0 V110.14 V (229.45%)21699.6 WDrop High
35 mm²125 A97 A47.69 V (99.36%)0.3 V78.67 V (163.89%)15499.7 WDrop High
50 mm²151 A118 A33.38 V (69.55%)14.6 V55.07 V (114.72%)10849.8 WDrop High
70 mm²192 A150 A23.85 V (49.68%)24.2 V39.33 V (81.95%)7749.9 WDrop High
95 mm²232 A181 A17.57 V (36.61%)30.4 V28.98 V (60.38%)5710.4 WDrop High
120 mm²269 A210 A13.91 V (28.98%)34.1 V22.95 V (47.8%)4520.8 WDrop High
150 mm²309 A241 A11.13 V (23.18%)36.9 V18.36 V (38.24%)3616.6 WDrop High
185 mm²353 A275 A9.02 V (18.8%)39.0 V14.88 V (31.01%)2932.4 WDrop High
240 mm²415 A324 A6.96 V (14.49%)41.0 V11.47 V (23.9%)2260.4 WDrop High
300 mm²477 A372 A5.56 V (11.59%)42.4 V9.18 V (19.12%)1808.3 WDrop High
400 mm²570 A445 A4.17 V (8.69%)43.8 V6.88 V (14.34%)1356.2 WDrop High

FAQ — 325 Amp Cable Size at 120 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 325A at 120 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 325A over 120m at 48V (voltage drop: 1.39V or 2.9%).

What is the power capacity of 325A at 48V?

At unity power factor, 325A at 48V supports 15.6 kW with a standard 350A circuit breaker.