⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

325 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 19.53V (2.83%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 19.87V (2.88%)
Voltage at Load670.5 VLine Loss: 10996.4 W
Max Power & Breaker388.41 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2409.28 V (349.17%)0.0 V3974.19 V (575.97%)1356225.0 WDrop High
2.5 mm²24 A18 A1445.57 V (209.5%)0.0 V2384.51 V (345.58%)813735.0 WDrop High
4 mm²32 A25 A903.48 V (130.94%)0.0 V1490.32 V (215.99%)508584.4 WDrop High
6 mm²41 A32 A602.32 V (87.29%)87.7 V993.55 V (143.99%)339056.2 WDrop High
10 mm²57 A44 A361.39 V (52.38%)328.6 V596.13 V (86.4%)203433.8 WDrop High
16 mm²76 A59 A225.87 V (32.73%)464.1 V372.58 V (54.0%)127146.1 WDrop High
25 mm²101 A78 A144.56 V (20.95%)545.4 V238.45 V (34.56%)81373.5 WDrop High
35 mm²125 A97 A103.25 V (14.96%)586.7 V170.32 V (24.68%)58123.9 WDrop High
50 mm²151 A118 A72.28 V (10.48%)617.7 V119.23 V (17.28%)40686.7 WDrop High
70 mm²192 A150 A51.63 V (7.48%)638.4 V85.16 V (12.34%)29062.0 WDrop High
95 mm²232 A181 A38.04 V (5.51%)652.0 V62.75 V (9.09%)21414.1 WDrop High
120 mm²269 A210 A30.12 V (4.36%)659.9 V49.68 V (7.2%)16952.8 WDrop High
150 mm²309 A241 A24.09 V (3.49%)665.9 V39.74 V (5.76%)13562.2 WDrop High
185 mm²353 A275 A19.53 V (2.83%)670.5 V32.22 V (4.67%)10996.4 W✓ OK (≤3%)
240 mm²415 A324 A15.06 V (2.18%)674.9 V24.84 V (3.6%)8476.4 W✓ OK (≤3%)
300 mm²477 A372 A12.05 V (1.75%)678.0 V19.87 V (2.88%)6781.1 W✓ OK (≤3%)
400 mm²570 A445 A9.03 V (1.31%)681.0 V14.9 V (2.16%)5085.8 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 325A at 300 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 300m at 690V (voltage drop: 19.53V or 2.83%).

What is the power capacity of 325A at 690V?

At unity power factor, 325A at 690V supports 388.41 kW with a standard 350A circuit breaker.