⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

325 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 17.57V (2.55%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 17.39V (2.52%)
Voltage at Load672.4 VLine Loss: 9889.1 W
Max Power & Breaker388.41 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2810.83 V (407.37%)0.0 V4636.56 V (671.96%)1582262.5 WDrop High
2.5 mm²24 A18 A1686.5 V (244.42%)0.0 V2781.93 V (403.18%)949357.5 WDrop High
4 mm²32 A25 A1054.06 V (152.76%)0.0 V1738.71 V (251.99%)593348.4 WDrop High
6 mm²41 A32 A702.71 V (101.84%)0.0 V1159.14 V (167.99%)395565.6 WDrop High
10 mm²57 A44 A421.62 V (61.1%)268.4 V695.48 V (100.79%)237339.4 WDrop High
16 mm²76 A59 A263.52 V (38.19%)426.5 V434.68 V (63.0%)148337.1 WDrop High
25 mm²101 A78 A168.65 V (24.44%)521.4 V278.19 V (40.32%)94935.8 WDrop High
35 mm²125 A97 A120.46 V (17.46%)569.5 V198.71 V (28.8%)67811.2 WDrop High
50 mm²151 A118 A84.32 V (12.22%)605.7 V139.1 V (20.16%)47467.9 WDrop High
70 mm²192 A150 A60.23 V (8.73%)629.8 V99.35 V (14.4%)33905.6 WDrop High
95 mm²232 A181 A44.38 V (6.43%)645.6 V73.21 V (10.61%)24983.1 WDrop High
120 mm²269 A210 A35.14 V (5.09%)654.9 V57.96 V (8.4%)19778.3 WDrop High
150 mm²309 A241 A28.11 V (4.07%)661.9 V46.37 V (6.72%)15822.6 WDrop High
185 mm²353 A275 A22.79 V (3.3%)667.2 V37.59 V (5.45%)12829.2 W~ ≤5%
240 mm²415 A324 A17.57 V (2.55%)672.4 V28.98 V (4.2%)9889.1 W✓ OK (≤3%)
300 mm²477 A372 A14.05 V (2.04%)675.9 V23.18 V (3.36%)7911.3 W✓ OK (≤3%)
400 mm²570 A445 A10.54 V (1.53%)679.5 V17.39 V (2.52%)5933.5 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 325A at 350 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 325A over 350m at 690V (voltage drop: 17.57V or 2.55%).

What is the power capacity of 325A at 690V?

At unity power factor, 325A at 690V supports 388.41 kW with a standard 350A circuit breaker.