350 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 350 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 11.35V (2.74%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 18.72V (4.51%)
Voltage at Load403.6 VLine Loss: 6881.4 W
Max Power & Breaker251.58 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3027.05 V (729.41%)0.0 V4993.21 V (1203.18%)1835050.0 WDrop High
2.5 mm²24 A18 A1816.23 V (437.65%)0.0 V2995.93 V (721.91%)1101030.0 WDrop High
4 mm²32 A25 A1135.14 V (273.53%)0.0 V1872.46 V (451.19%)688143.7 WDrop High
6 mm²41 A32 A756.76 V (182.35%)0.0 V1248.3 V (300.8%)458762.5 WDrop High
10 mm²57 A44 A454.06 V (109.41%)0.0 V748.98 V (180.48%)275257.5 WDrop High
16 mm²76 A59 A283.79 V (68.38%)131.2 V468.11 V (112.8%)172035.9 WDrop High
25 mm²101 A78 A181.62 V (43.76%)233.4 V299.59 V (72.19%)110103.0 WDrop High
35 mm²125 A97 A129.73 V (31.26%)285.3 V213.99 V (51.57%)78645.0 WDrop High
50 mm²151 A118 A90.81 V (21.88%)324.2 V149.8 V (36.1%)55051.5 WDrop High
70 mm²192 A150 A64.87 V (15.63%)350.1 V107.0 V (25.78%)39322.5 WDrop High
95 mm²232 A181 A47.8 V (11.52%)367.2 V78.84 V (19.0%)28974.5 WDrop High
120 mm²269 A210 A37.84 V (9.12%)377.2 V62.42 V (15.04%)22938.1 WDrop High
150 mm²309 A241 A30.27 V (7.29%)384.7 V49.93 V (12.03%)18350.5 WDrop High
185 mm²353 A275 A24.54 V (5.91%)390.5 V40.49 V (9.76%)14878.8 WDrop High
240 mm²415 A324 A18.92 V (4.56%)396.1 V31.21 V (7.52%)11469.1 W~ ≤5%
300 mm²477 A372 A15.14 V (3.65%)399.9 V24.97 V (6.02%)9175.2 W~ ≤5%
400 mm²570 A445 A11.35 V (2.74%)403.6 V18.72 V (4.51%)6881.4 W✓ OK (≤3%)

FAQ — 350 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 350A at 350 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 350A over 350m at 415V (voltage drop: 11.35V or 2.74%).

What is the power capacity of 350A at 415V?

At unity power factor, 350A at 415V supports 251.58 kW with a standard 350A circuit breaker.