375 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 1.07V (2.23%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.29V (11.03%)
Voltage at Load46.9 VLine Loss: 401.3 W
Max Power & Breaker18.0 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A856.0 V (1783.33%)0.0 V1412.0 V (2941.67%)321000.0 WDrop High
2.5 mm²24 A18 A513.6 V (1070.0%)0.0 V847.2 V (1765.0%)192600.0 WDrop High
4 mm²32 A25 A321.0 V (668.75%)0.0 V529.5 V (1103.12%)120375.0 WDrop High
6 mm²41 A32 A214.0 V (445.83%)0.0 V353.0 V (735.42%)80250.0 WDrop High
10 mm²57 A44 A128.4 V (267.5%)0.0 V211.8 V (441.25%)48150.0 WDrop High
16 mm²76 A59 A80.25 V (167.19%)0.0 V132.38 V (275.78%)30093.8 WDrop High
25 mm²101 A78 A51.36 V (107.0%)0.0 V84.72 V (176.5%)19260.0 WDrop High
35 mm²125 A97 A36.69 V (76.43%)11.3 V60.51 V (126.07%)13757.1 WDrop High
50 mm²151 A118 A25.68 V (53.5%)22.3 V42.36 V (88.25%)9630.0 WDrop High
70 mm²192 A150 A18.34 V (38.21%)29.7 V30.26 V (63.04%)6878.6 WDrop High
95 mm²232 A181 A13.52 V (28.16%)34.5 V22.29 V (46.45%)5068.4 WDrop High
120 mm²269 A210 A10.7 V (22.29%)37.3 V17.65 V (36.77%)4012.5 WDrop High
150 mm²309 A241 A8.56 V (17.83%)39.4 V14.12 V (29.42%)3210.0 WDrop High
185 mm²353 A275 A6.94 V (14.46%)41.1 V11.45 V (23.85%)2602.7 WDrop High
240 mm²415 A324 A5.35 V (11.15%)42.6 V8.82 V (18.39%)2006.2 WDrop High
300 mm²477 A372 A4.28 V (8.92%)43.7 V7.06 V (14.71%)1605.0 WDrop High
400 mm²570 A445 A3.21 V (6.69%)44.8 V5.29 V (11.03%)1203.8 WDrop High

FAQ — 375 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 375A at 80 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 375A over 80m at 48V (voltage drop: 1.07V or 2.23%).

What is the power capacity of 375A at 48V?

At unity power factor, 375A at 48V supports 18.0 kW with a standard 400A circuit breaker.