⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

400 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 6.18V (1.49%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.11V (1.47%)
Voltage at Load408.8 VLine Loss: 4280.0 W
Max Power & Breaker287.52 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A988.42 V (238.17%)0.0 V1630.44 V (392.88%)684800.0 WDrop High
2.5 mm²24 A18 A593.05 V (142.9%)0.0 V978.26 V (235.73%)410880.0 WDrop High
4 mm²32 A25 A370.66 V (89.32%)44.3 V611.41 V (147.33%)256800.0 WDrop High
6 mm²41 A32 A247.11 V (59.54%)167.9 V407.61 V (98.22%)171200.0 WDrop High
10 mm²57 A44 A148.26 V (35.73%)266.7 V244.57 V (58.93%)102720.0 WDrop High
16 mm²76 A59 A92.66 V (22.33%)322.3 V152.85 V (36.83%)64200.0 WDrop High
25 mm²101 A78 A59.31 V (14.29%)355.7 V97.83 V (23.57%)41088.0 WDrop High
35 mm²125 A97 A42.36 V (10.21%)372.6 V69.88 V (16.84%)29348.6 WDrop High
50 mm²151 A118 A29.65 V (7.15%)385.3 V48.91 V (11.79%)20544.0 WDrop High
70 mm²192 A150 A21.18 V (5.1%)393.8 V34.94 V (8.42%)14674.3 WDrop High
95 mm²232 A181 A15.61 V (3.76%)399.4 V25.74 V (6.2%)10812.6 WDrop High
120 mm²269 A210 A12.36 V (2.98%)402.6 V20.38 V (4.91%)8560.0 WDrop High
150 mm²309 A241 A9.88 V (2.38%)405.1 V16.3 V (3.93%)6848.0 WDrop High
185 mm²353 A275 A8.01 V (1.93%)407.0 V13.22 V (3.19%)5552.4 WDrop High
240 mm²415 A324 A6.18 V (1.49%)408.8 V10.19 V (2.46%)4280.0 W✓ OK (≤3%)
300 mm²477 A372 A4.94 V (1.19%)410.1 V8.15 V (1.96%)3424.0 W✓ OK (≤3%)
400 mm²570 A445 A3.71 V (0.89%)411.3 V6.11 V (1.47%)2568.0 W✓ OK (≤3%)

FAQ — 400 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 400A at 100 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 400A over 100m at 415V (voltage drop: 6.18V or 1.49%).

What is the power capacity of 400A at 415V?

At unity power factor, 400A at 415V supports 287.52 kW with a standard 400A circuit breaker.