⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

400 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 4.94V (0.72%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.89V (0.71%)
Voltage at Load685.1 VLine Loss: 3424.0 W
Max Power & Breaker478.05 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A790.74 V (114.6%)0.0 V1304.35 V (189.04%)547840.0 WDrop High
2.5 mm²24 A18 A474.44 V (68.76%)215.6 V782.61 V (113.42%)328704.0 WDrop High
4 mm²32 A25 A296.53 V (42.97%)393.5 V489.13 V (70.89%)205440.0 WDrop High
6 mm²41 A32 A197.68 V (28.65%)492.3 V326.09 V (47.26%)136960.0 WDrop High
10 mm²57 A44 A118.61 V (17.19%)571.4 V195.65 V (28.36%)82176.0 WDrop High
16 mm²76 A59 A74.13 V (10.74%)615.9 V122.28 V (17.72%)51360.0 WDrop High
25 mm²101 A78 A47.44 V (6.88%)642.6 V78.26 V (11.34%)32870.4 WDrop High
35 mm²125 A97 A33.89 V (4.91%)656.1 V55.9 V (8.1%)23478.9 WDrop High
50 mm²151 A118 A23.72 V (3.44%)666.3 V39.13 V (5.67%)16435.2 WDrop High
70 mm²192 A150 A16.94 V (2.46%)673.1 V27.95 V (4.05%)11739.4 WDrop High
95 mm²232 A181 A12.49 V (1.81%)677.5 V20.59 V (2.98%)8650.1 WDrop High
120 mm²269 A210 A9.88 V (1.43%)680.1 V16.3 V (2.36%)6848.0 WDrop High
150 mm²309 A241 A7.91 V (1.15%)682.1 V13.04 V (1.89%)5478.4 WDrop High
185 mm²353 A275 A6.41 V (0.93%)683.6 V10.58 V (1.53%)4441.9 WDrop High
240 mm²415 A324 A4.94 V (0.72%)685.1 V8.15 V (1.18%)3424.0 W✓ OK (≤3%)
300 mm²477 A372 A3.95 V (0.57%)686.0 V6.52 V (0.95%)2739.2 W✓ OK (≤3%)
400 mm²570 A445 A2.97 V (0.43%)687.0 V4.89 V (0.71%)2054.4 W✓ OK (≤3%)

FAQ — 400 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 400A at 80 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 400A over 80m at 690V (voltage drop: 4.94V or 0.72%).

What is the power capacity of 400A at 690V?

At unity power factor, 400A at 690V supports 478.05 kW with a standard 400A circuit breaker.