425 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 6.3V (1.52%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.8V (1.88%)
Voltage at Load408.7 VLine Loss: 4638.4 W
Max Power & Breaker305.49 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1260.24 V (303.67%)0.0 V2078.81 V (500.92%)927690.0 WDrop High
2.5 mm²24 A18 A756.14 V (182.2%)0.0 V1247.28 V (300.55%)556614.0 WDrop High
4 mm²32 A25 A472.59 V (113.88%)0.0 V779.55 V (187.84%)347883.8 WDrop High
6 mm²41 A32 A315.06 V (75.92%)99.9 V519.7 V (125.23%)231922.5 WDrop High
10 mm²57 A44 A189.04 V (45.55%)226.0 V311.82 V (75.14%)139153.5 WDrop High
16 mm²76 A59 A118.15 V (28.47%)296.9 V194.89 V (46.96%)86970.9 WDrop High
25 mm²101 A78 A75.61 V (18.22%)339.4 V124.73 V (30.06%)55661.4 WDrop High
35 mm²125 A97 A54.01 V (13.01%)361.0 V89.09 V (21.47%)39758.1 WDrop High
50 mm²151 A118 A37.81 V (9.11%)377.2 V62.36 V (15.03%)27830.7 WDrop High
70 mm²192 A150 A27.01 V (6.51%)388.0 V44.55 V (10.73%)19879.1 WDrop High
95 mm²232 A181 A19.9 V (4.79%)395.1 V32.82 V (7.91%)14647.7 WDrop High
120 mm²269 A210 A15.75 V (3.8%)399.2 V25.99 V (6.26%)11596.1 WDrop High
150 mm²309 A241 A12.6 V (3.04%)402.4 V20.79 V (5.01%)9276.9 WDrop High
185 mm²353 A275 A10.22 V (2.46%)404.8 V16.86 V (4.06%)7521.8 WDrop High
240 mm²415 A324 A7.88 V (1.9%)407.1 V12.99 V (3.13%)5798.1 WDrop High
300 mm²477 A372 A6.3 V (1.52%)408.7 V10.39 V (2.5%)4638.4 W✓ OK (≤3%)
400 mm²570 A445 A4.73 V (1.14%)410.3 V7.8 V (1.88%)3478.8 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 425A at 120 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 120m at 415V (voltage drop: 6.3V or 1.52%).

What is the power capacity of 425A at 415V?

At unity power factor, 425A at 415V supports 305.49 kW with a standard 450A circuit breaker.