425 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 9.85V (2.37%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 16.24V (3.91%)
Voltage at Load405.2 VLine Loss: 7247.6 W
Max Power & Breaker305.49 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2625.5 V (632.65%)0.0 V4330.85 V (1043.58%)1932687.5 WDrop High
2.5 mm²24 A18 A1575.3 V (379.59%)0.0 V2598.51 V (626.15%)1159612.5 WDrop High
4 mm²32 A25 A984.56 V (237.24%)0.0 V1624.07 V (391.34%)724757.8 WDrop High
6 mm²41 A32 A656.38 V (158.16%)0.0 V1082.71 V (260.89%)483171.9 WDrop High
10 mm²57 A44 A393.83 V (94.9%)21.2 V649.63 V (156.54%)289903.1 WDrop High
16 mm²76 A59 A246.14 V (59.31%)168.9 V406.02 V (97.84%)181189.5 WDrop High
25 mm²101 A78 A157.53 V (37.96%)257.5 V259.85 V (62.61%)115961.2 WDrop High
35 mm²125 A97 A112.52 V (27.11%)302.5 V185.61 V (44.72%)82829.5 WDrop High
50 mm²151 A118 A78.77 V (18.98%)336.2 V129.93 V (31.31%)57980.6 WDrop High
70 mm²192 A150 A56.26 V (13.56%)358.7 V92.8 V (22.36%)41414.7 WDrop High
95 mm²232 A181 A41.46 V (9.99%)373.5 V68.38 V (16.48%)30516.1 WDrop High
120 mm²269 A210 A32.82 V (7.91%)382.2 V54.14 V (13.04%)24158.6 WDrop High
150 mm²309 A241 A26.26 V (6.33%)388.7 V43.31 V (10.44%)19326.9 WDrop High
185 mm²353 A275 A21.29 V (5.13%)393.7 V35.11 V (8.46%)15670.4 WDrop High
240 mm²415 A324 A16.41 V (3.95%)398.6 V27.07 V (6.52%)12079.3 WDrop High
300 mm²477 A372 A13.13 V (3.16%)401.9 V21.65 V (5.22%)9663.4 W~ ≤5%
400 mm²570 A445 A9.85 V (2.37%)405.2 V16.24 V (3.91%)7247.6 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 425A at 250 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 425A over 250m at 415V (voltage drop: 9.85V or 2.37%).

What is the power capacity of 425A at 415V?

At unity power factor, 425A at 415V supports 305.49 kW with a standard 450A circuit breaker.