⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

425 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 11.81V (2.85%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 19.49V (4.7%)
Voltage at Load403.2 VLine Loss: 8697.1 W
Max Power & Breaker305.49 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3150.6 V (759.18%)0.0 V5197.02 V (1252.29%)2319225.0 WDrop High
2.5 mm²24 A18 A1890.36 V (455.51%)0.0 V3118.21 V (751.38%)1391535.0 WDrop High
4 mm²32 A25 A1181.48 V (284.69%)0.0 V1948.88 V (469.61%)869709.4 WDrop High
6 mm²41 A32 A787.65 V (189.8%)0.0 V1299.25 V (313.07%)579806.2 WDrop High
10 mm²57 A44 A472.59 V (113.88%)0.0 V779.55 V (187.84%)347883.8 WDrop High
16 mm²76 A59 A295.37 V (71.17%)119.6 V487.22 V (117.4%)217427.3 WDrop High
25 mm²101 A78 A189.04 V (45.55%)226.0 V311.82 V (75.14%)139153.5 WDrop High
35 mm²125 A97 A135.03 V (32.54%)280.0 V222.73 V (53.67%)99395.4 WDrop High
50 mm²151 A118 A94.52 V (22.78%)320.5 V155.91 V (37.57%)69576.7 WDrop High
70 mm²192 A150 A67.51 V (16.27%)347.5 V111.36 V (26.83%)49697.7 WDrop High
95 mm²232 A181 A49.75 V (11.99%)365.3 V82.06 V (19.77%)36619.3 WDrop High
120 mm²269 A210 A39.38 V (9.49%)375.6 V64.96 V (15.65%)28990.3 WDrop High
150 mm²309 A241 A31.51 V (7.59%)383.5 V51.97 V (12.52%)23192.2 WDrop High
185 mm²353 A275 A25.55 V (6.16%)389.5 V42.14 V (10.15%)18804.5 WDrop High
240 mm²415 A324 A19.69 V (4.74%)395.3 V32.48 V (7.83%)14495.2 WDrop High
300 mm²477 A372 A15.75 V (3.8%)399.2 V25.99 V (6.26%)11596.1 W~ ≤5%
400 mm²570 A445 A11.81 V (2.85%)403.2 V19.49 V (4.7%)8697.1 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 425A at 300 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 425A over 300m at 415V (voltage drop: 11.81V or 2.85%).

What is the power capacity of 425A at 415V?

At unity power factor, 425A at 415V supports 305.49 kW with a standard 450A circuit breaker.