425 Amp Cable Size at 40 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.91V (1.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.0V (6.25%)
Voltage at Load47.1 VLine Loss: 386.6 W
Max Power & Breaker20.4 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A485.07 V (1010.56%)0.0 V800.13 V (1666.94%)206153.3 WDrop High
2.5 mm²24 A18 A291.04 V (606.33%)0.0 V480.08 V (1000.17%)123692.0 WDrop High
4 mm²32 A25 A181.9 V (378.96%)0.0 V300.05 V (625.1%)77307.5 WDrop High
6 mm²41 A32 A121.27 V (252.64%)0.0 V200.03 V (416.74%)51538.3 WDrop High
10 mm²57 A44 A72.76 V (151.58%)0.0 V120.02 V (250.04%)30923.0 WDrop High
16 mm²76 A59 A45.48 V (94.74%)2.5 V75.01 V (156.28%)19326.9 WDrop High
25 mm²101 A78 A29.1 V (60.63%)18.9 V48.01 V (100.02%)12369.2 WDrop High
35 mm²125 A97 A20.79 V (43.31%)27.2 V34.29 V (71.44%)8835.1 WDrop High
50 mm²151 A118 A14.55 V (30.32%)33.4 V24.0 V (50.01%)6184.6 WDrop High
70 mm²192 A150 A10.39 V (21.65%)37.6 V17.15 V (35.72%)4417.6 WDrop High
95 mm²232 A181 A7.66 V (15.96%)40.3 V12.63 V (26.32%)3255.1 WDrop High
120 mm²269 A210 A6.06 V (12.63%)41.9 V10.0 V (20.84%)2576.9 WDrop High
150 mm²309 A241 A4.85 V (10.11%)43.1 V8.0 V (16.67%)2061.5 WDrop High
185 mm²353 A275 A3.93 V (8.19%)44.1 V6.49 V (13.52%)1671.5 WDrop High
240 mm²415 A324 A3.03 V (6.32%)45.0 V5.0 V (10.42%)1288.5 WDrop High
300 mm²477 A372 A2.43 V (5.05%)45.6 V4.0 V (8.33%)1030.8 WDrop High
400 mm²570 A445 A1.82 V (3.79%)46.2 V3.0 V (6.25%)773.1 W~ ≤5%

FAQ — 425 Amp Cable Size at 40 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 425A at 40 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 425A over 40m at 48V (voltage drop: 0.91V or 1.9%).

What is the power capacity of 425A at 48V?

At unity power factor, 425A at 48V supports 20.4 kW with a standard 450A circuit breaker.