425 Amp Cable Size at 45 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.02V (2.13%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.38V (7.03%)
Voltage at Load47.0 VLine Loss: 434.9 W
Max Power & Breaker20.4 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A545.7 V (1136.88%)0.0 V900.15 V (1875.31%)231922.5 WDrop High
2.5 mm²24 A18 A327.42 V (682.12%)0.0 V540.09 V (1125.19%)139153.5 WDrop High
4 mm²32 A25 A204.64 V (426.33%)0.0 V337.56 V (703.24%)86970.9 WDrop High
6 mm²41 A32 A136.43 V (284.22%)0.0 V225.04 V (468.83%)57980.6 WDrop High
10 mm²57 A44 A81.86 V (170.53%)0.0 V135.02 V (281.3%)34788.4 WDrop High
16 mm²76 A59 A51.16 V (106.58%)0.0 V84.39 V (175.81%)21742.7 WDrop High
25 mm²101 A78 A32.74 V (68.21%)15.3 V54.01 V (112.52%)13915.4 WDrop High
35 mm²125 A97 A23.39 V (48.72%)24.6 V38.58 V (80.37%)9939.5 WDrop High
50 mm²151 A118 A16.37 V (34.11%)31.6 V27.0 V (56.26%)6957.7 WDrop High
70 mm²192 A150 A11.69 V (24.36%)36.3 V19.29 V (40.19%)4969.8 WDrop High
95 mm²232 A181 A8.62 V (17.95%)39.4 V14.21 V (29.61%)3661.9 WDrop High
120 mm²269 A210 A6.82 V (14.21%)41.2 V11.25 V (23.44%)2899.0 WDrop High
150 mm²309 A241 A5.46 V (11.37%)42.5 V9.0 V (18.75%)2319.2 WDrop High
185 mm²353 A275 A4.42 V (9.22%)43.6 V7.3 V (15.21%)1880.5 WDrop High
240 mm²415 A324 A3.41 V (7.11%)44.6 V5.63 V (11.72%)1449.5 WDrop High
300 mm²477 A372 A2.73 V (5.68%)45.3 V4.5 V (9.38%)1159.6 WDrop High
400 mm²570 A445 A2.05 V (4.26%)46.0 V3.38 V (7.03%)869.7 W~ ≤5%

FAQ — 425 Amp Cable Size at 45 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 425A at 45 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 425A over 45m at 48V (voltage drop: 1.02V or 2.13%).

What is the power capacity of 425A at 48V?

At unity power factor, 425A at 48V supports 20.4 kW with a standard 450A circuit breaker.