425 Amp Cable Size at 50 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.14V (2.37%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.75V (7.81%)
Voltage at Load46.9 VLine Loss: 483.1 W
Max Power & Breaker20.4 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A606.33 V (1263.19%)0.0 V1000.17 V (2083.68%)257691.7 WDrop High
2.5 mm²24 A18 A363.8 V (757.92%)0.0 V600.1 V (1250.21%)154615.0 WDrop High
4 mm²32 A25 A227.37 V (473.7%)0.0 V375.06 V (781.38%)96634.4 WDrop High
6 mm²41 A32 A151.58 V (315.8%)0.0 V250.04 V (520.92%)64422.9 WDrop High
10 mm²57 A44 A90.95 V (189.48%)0.0 V150.03 V (312.55%)38653.7 WDrop High
16 mm²76 A59 A56.84 V (118.42%)0.0 V93.77 V (195.35%)24158.6 WDrop High
25 mm²101 A78 A36.38 V (75.79%)11.6 V60.01 V (125.02%)15461.5 WDrop High
35 mm²125 A97 A25.99 V (54.14%)22.0 V42.86 V (89.3%)11043.9 WDrop High
50 mm²151 A118 A18.19 V (37.9%)29.8 V30.0 V (62.51%)7730.7 WDrop High
70 mm²192 A150 A12.99 V (27.07%)35.0 V21.43 V (44.65%)5522.0 WDrop High
95 mm²232 A181 A9.57 V (19.95%)38.4 V15.79 V (32.9%)4068.8 WDrop High
120 mm²269 A210 A7.58 V (15.79%)40.4 V12.5 V (26.05%)3221.1 WDrop High
150 mm²309 A241 A6.06 V (12.63%)41.9 V10.0 V (20.84%)2576.9 WDrop High
185 mm²353 A275 A4.92 V (10.24%)43.1 V8.11 V (16.89%)2089.4 WDrop High
240 mm²415 A324 A3.79 V (7.89%)44.2 V6.25 V (13.02%)1610.6 WDrop High
300 mm²477 A372 A3.03 V (6.32%)45.0 V5.0 V (10.42%)1288.5 WDrop High
400 mm²570 A445 A2.27 V (4.74%)45.7 V3.75 V (7.81%)966.3 W~ ≤5%

FAQ — 425 Amp Cable Size at 50 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 425A at 50 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 425A over 50m at 48V (voltage drop: 1.14V or 2.37%).

What is the power capacity of 425A at 48V?

At unity power factor, 425A at 48V supports 20.4 kW with a standard 450A circuit breaker.