425 Amp Cable Size at 20 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 1.21V (2.53%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.5V (3.13%)
Voltage at Load46.8 VLine Loss: 515.4 W
Max Power & Breaker20.4 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A242.53 V (505.28%)0.0 V400.07 V (833.47%)103076.7 WDrop High
2.5 mm²24 A18 A145.52 V (303.17%)0.0 V240.04 V (500.08%)61846.0 WDrop High
4 mm²32 A25 A90.95 V (189.48%)0.0 V150.03 V (312.55%)38653.8 WDrop High
6 mm²41 A32 A60.63 V (126.32%)0.0 V100.02 V (208.37%)25769.2 WDrop High
10 mm²57 A44 A36.38 V (75.79%)11.6 V60.01 V (125.02%)15461.5 WDrop High
16 mm²76 A59 A22.74 V (47.37%)25.3 V37.51 V (78.14%)9663.4 WDrop High
25 mm²101 A78 A14.55 V (30.32%)33.4 V24.0 V (50.01%)6184.6 WDrop High
35 mm²125 A97 A10.39 V (21.65%)37.6 V17.15 V (35.72%)4417.6 WDrop High
50 mm²151 A118 A7.28 V (15.16%)40.7 V12.0 V (25.0%)3092.3 WDrop High
70 mm²192 A150 A5.2 V (10.83%)42.8 V8.57 V (17.86%)2208.8 WDrop High
95 mm²232 A181 A3.83 V (7.98%)44.2 V6.32 V (13.16%)1627.5 WDrop High
120 mm²269 A210 A3.03 V (6.32%)45.0 V5.0 V (10.42%)1288.5 WDrop High
150 mm²309 A241 A2.43 V (5.05%)45.6 V4.0 V (8.33%)1030.8 WDrop High
185 mm²353 A275 A1.97 V (4.1%)46.0 V3.24 V (6.76%)835.8 WDrop High
240 mm²415 A324 A1.52 V (3.16%)46.5 V2.5 V (5.21%)644.2 WDrop High
300 mm²477 A372 A1.21 V (2.53%)46.8 V2.0 V (4.17%)515.4 W✓ OK (≤3%)
400 mm²570 A445 A0.91 V (1.89%)47.1 V1.5 V (3.13%)386.5 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 20 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 425A at 20 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 20m at 48V (voltage drop: 1.21V or 2.53%).

What is the power capacity of 425A at 48V?

At unity power factor, 425A at 48V supports 20.4 kW with a standard 450A circuit breaker.