⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

425 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.91V (1.89%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.13V (2.34%)
Voltage at Load47.1 VLine Loss: 386.5 W
Max Power & Breaker20.4 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A181.9 V (378.96%)0.0 V300.05 V (625.1%)77307.5 WDrop High
2.5 mm²24 A18 A109.14 V (227.38%)0.0 V180.03 V (375.06%)46384.5 WDrop High
4 mm²32 A25 A68.21 V (142.11%)0.0 V112.52 V (234.41%)28990.3 WDrop High
6 mm²41 A32 A45.48 V (94.74%)2.5 V75.01 V (156.28%)19326.9 WDrop High
10 mm²57 A44 A27.29 V (56.84%)20.7 V45.01 V (93.77%)11596.1 WDrop High
16 mm²76 A59 A17.05 V (35.53%)30.9 V28.13 V (58.6%)7247.6 WDrop High
25 mm²101 A78 A10.91 V (22.74%)37.1 V18.0 V (37.51%)4638.4 WDrop High
35 mm²125 A97 A7.8 V (16.24%)40.2 V12.86 V (26.79%)3313.2 WDrop High
50 mm²151 A118 A5.46 V (11.37%)42.5 V9.0 V (18.75%)2319.2 WDrop High
70 mm²192 A150 A3.9 V (8.12%)44.1 V6.43 V (13.4%)1656.6 WDrop High
95 mm²232 A181 A2.87 V (5.98%)45.1 V4.74 V (9.87%)1220.6 WDrop High
120 mm²269 A210 A2.27 V (4.74%)45.7 V3.75 V (7.81%)966.3 WDrop High
150 mm²309 A241 A1.82 V (3.79%)46.2 V3.0 V (6.25%)773.1 WDrop High
185 mm²353 A275 A1.47 V (3.07%)46.5 V2.43 V (5.07%)626.8 WDrop High
240 mm²415 A324 A1.14 V (2.37%)46.9 V1.88 V (3.91%)483.2 WDrop High
300 mm²477 A372 A0.91 V (1.89%)47.1 V1.5 V (3.13%)386.5 W✓ OK (≤3%)
400 mm²570 A445 A0.68 V (1.42%)47.3 V1.13 V (2.34%)289.9 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 15 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 425A at 15 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 15m at 48V (voltage drop: 0.91V or 1.89%).

What is the power capacity of 425A at 48V?

At unity power factor, 425A at 48V supports 20.4 kW with a standard 450A circuit breaker.