⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

425 Amp Cable Size at 60 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 60 m (196.9 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.36V (2.84%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.5V (9.38%)
Voltage at Load46.6 VLine Loss: 579.8 W
Max Power & Breaker20.4 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A727.6 V (1515.83%)0.0 V1200.2 V (2500.42%)309230.0 WDrop High
2.5 mm²24 A18 A436.56 V (909.5%)0.0 V720.12 V (1500.25%)185538.0 WDrop High
4 mm²32 A25 A272.85 V (568.44%)0.0 V450.07 V (937.66%)115961.2 WDrop High
6 mm²41 A32 A181.9 V (378.96%)0.0 V300.05 V (625.1%)77307.5 WDrop High
10 mm²57 A44 A109.14 V (227.38%)0.0 V180.03 V (375.06%)46384.5 WDrop High
16 mm²76 A59 A68.21 V (142.11%)0.0 V112.52 V (234.41%)28990.3 WDrop High
25 mm²101 A78 A43.66 V (90.95%)4.3 V72.01 V (150.02%)18553.8 WDrop High
35 mm²125 A97 A31.18 V (64.96%)16.8 V51.44 V (107.16%)13252.7 WDrop High
50 mm²151 A118 A21.83 V (45.48%)26.2 V36.01 V (75.01%)9276.9 WDrop High
70 mm²192 A150 A15.59 V (32.48%)32.4 V25.72 V (53.58%)6626.4 WDrop High
95 mm²232 A181 A11.49 V (23.93%)36.5 V18.95 V (39.48%)4882.6 WDrop High
120 mm²269 A210 A9.09 V (18.95%)38.9 V15.0 V (31.26%)3865.4 WDrop High
150 mm²309 A241 A7.28 V (15.16%)40.7 V12.0 V (25.0%)3092.3 WDrop High
185 mm²353 A275 A5.9 V (12.29%)42.1 V9.73 V (20.27%)2507.3 WDrop High
240 mm²415 A324 A4.55 V (9.47%)43.5 V7.5 V (15.63%)1932.7 WDrop High
300 mm²477 A372 A3.64 V (7.58%)44.4 V6.0 V (12.5%)1546.2 WDrop High
400 mm²570 A445 A2.73 V (5.68%)45.3 V4.5 V (9.38%)1159.6 WDrop High

FAQ — 425 Amp Cable Size at 60 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 425A at 60 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 425A over 60m at 48V (voltage drop: 1.36V or 2.84%).

What is the power capacity of 425A at 48V?

At unity power factor, 425A at 48V supports 20.4 kW with a standard 450A circuit breaker.