425 Amp Cable Size at 400 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 7.88V (1.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 25.99V (6.26%)
Voltage at Load407.1 VLine Loss: 5798.1 W
Max Power & Breaker305.49 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4200.8 V (1012.24%)0.0 V6929.36 V (1669.72%)3092300.0 WDrop High
2.5 mm²24 A18 A2520.48 V (607.34%)0.0 V4157.61 V (1001.83%)1855380.0 WDrop High
4 mm²32 A25 A1575.3 V (379.59%)0.0 V2598.51 V (626.15%)1159612.5 WDrop High
6 mm²41 A32 A1050.2 V (253.06%)0.0 V1732.34 V (417.43%)773075.0 WDrop High
10 mm²57 A44 A630.12 V (151.84%)0.0 V1039.4 V (250.46%)463845.0 WDrop High
16 mm²76 A59 A393.83 V (94.9%)21.2 V649.63 V (156.54%)289903.1 WDrop High
25 mm²101 A78 A252.05 V (60.73%)163.0 V415.76 V (100.18%)185538.0 WDrop High
35 mm²125 A97 A180.03 V (43.38%)235.0 V296.97 V (71.56%)132527.1 WDrop High
50 mm²151 A118 A126.02 V (30.37%)289.0 V207.88 V (50.09%)92769.0 WDrop High
70 mm²192 A150 A90.02 V (21.69%)325.0 V148.49 V (35.78%)66263.6 WDrop High
95 mm²232 A181 A66.33 V (15.98%)348.7 V109.41 V (26.36%)48825.8 WDrop High
120 mm²269 A210 A52.51 V (12.65%)362.5 V86.62 V (20.87%)38653.7 WDrop High
150 mm²309 A241 A42.01 V (10.12%)373.0 V69.29 V (16.7%)30923.0 WDrop High
185 mm²353 A275 A34.06 V (8.21%)380.9 V56.18 V (13.54%)25072.7 WDrop High
240 mm²415 A324 A26.26 V (6.33%)388.7 V43.31 V (10.44%)19326.9 WDrop High
300 mm²477 A372 A21.0 V (5.06%)394.0 V34.65 V (8.35%)15461.5 WDrop High
400 mm²570 A445 A15.75 V (3.8%)399.2 V25.99 V (6.26%)11596.1 W~ ≤5%

FAQ — 425 Amp Cable Size at 400 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 425A at 400 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 425A over 400m at 415V (voltage drop: 7.88V or 1.9%).

What is the power capacity of 425A at 415V?

At unity power factor, 425A at 415V supports 305.49 kW with a standard 450A circuit breaker.