45 Amp Cable Size at 150 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 5.78V (2.51%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 6.81V (2.96%)
Voltage at Load224.2 VLine Loss: 260.0 W
Max Power & Breaker10.35 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A192.6 V (83.74%)37.4 V317.7 V (138.13%)8667.0 WDrop High
2.5 mm²24 A18 A115.56 V (50.24%)114.4 V190.62 V (82.88%)5200.2 WDrop High
4 mm²32 A25 A72.22 V (31.4%)157.8 V119.14 V (51.8%)3250.1 WDrop High
6 mm²41 A32 A48.15 V (20.93%)181.8 V79.42 V (34.53%)2166.8 WDrop High
10 mm²57 A44 A28.89 V (12.56%)201.1 V47.65 V (20.72%)1300.0 WDrop High
16 mm²76 A59 A18.06 V (7.85%)211.9 V29.78 V (12.95%)812.5 WDrop High
25 mm²101 A78 A11.56 V (5.02%)218.4 V19.06 V (8.29%)520.0 WDrop High
35 mm²125 A97 A8.25 V (3.59%)221.7 V13.62 V (5.92%)371.4 W~ ≤5%
50 mm²151 A118 A5.78 V (2.51%)224.2 V9.53 V (4.14%)260.0 W✓ OK (≤3%)
70 mm²192 A150 A4.13 V (1.79%)225.9 V6.81 V (2.96%)185.7 W✓ OK (≤3%)
95 mm²232 A181 A3.04 V (1.32%)227.0 V5.02 V (2.18%)136.8 W✓ OK (≤3%)
120 mm²269 A210 A2.41 V (1.05%)227.6 V3.97 V (1.73%)108.3 W✓ OK (≤3%)
150 mm²309 A241 A1.93 V (0.84%)228.1 V3.18 V (1.38%)86.7 W✓ OK (≤3%)
185 mm²353 A275 A1.56 V (0.68%)228.4 V2.58 V (1.12%)70.3 W✓ OK (≤3%)
240 mm²415 A324 A1.2 V (0.52%)228.8 V1.99 V (0.86%)54.2 W✓ OK (≤3%)
300 mm²477 A372 A0.96 V (0.42%)229.0 V1.59 V (0.69%)43.3 W✓ OK (≤3%)
400 mm²570 A445 A0.72 V (0.31%)229.3 V1.19 V (0.52%)32.5 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 150 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 45A at 150 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 45A over 150m at 230V (voltage drop: 5.78V or 2.51%).

What is the power capacity of 45A at 230V?

At unity power factor, 45A at 230V supports 10.35 kW with a standard 45A circuit breaker.