⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

45 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)50 mm²Drop: 11.68V (2.81%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 10.14V (2.44%)
Voltage at Load403.3 VLine Loss: 910.0 W
Max Power & Breaker32.35 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A389.19 V (93.78%)25.8 V641.98 V (154.7%)30334.5 WDrop High
2.5 mm²24 A18 A233.52 V (56.27%)181.5 V385.19 V (92.82%)18200.7 WDrop High
4 mm²32 A25 A145.95 V (35.17%)269.1 V240.74 V (58.01%)11375.4 WDrop High
6 mm²41 A32 A97.3 V (23.45%)317.7 V160.5 V (38.67%)7583.6 WDrop High
10 mm²57 A44 A58.38 V (14.07%)356.6 V96.3 V (23.2%)4550.2 WDrop High
16 mm²76 A59 A36.49 V (8.79%)378.5 V60.19 V (14.5%)2843.9 WDrop High
25 mm²101 A78 A23.35 V (5.63%)391.6 V38.52 V (9.28%)1820.1 WDrop High
35 mm²125 A97 A16.68 V (4.02%)398.3 V27.51 V (6.63%)1300.0 W~ ≤5%
50 mm²151 A118 A11.68 V (2.81%)403.3 V19.26 V (4.64%)910.0 W✓ OK (≤3%)
70 mm²192 A150 A8.34 V (2.01%)406.7 V13.76 V (3.31%)650.0 W✓ OK (≤3%)
95 mm²232 A181 A6.15 V (1.48%)408.9 V10.14 V (2.44%)479.0 W✓ OK (≤3%)
120 mm²269 A210 A4.86 V (1.17%)410.1 V8.02 V (1.93%)379.2 W✓ OK (≤3%)
150 mm²309 A241 A3.89 V (0.94%)411.1 V6.42 V (1.55%)303.3 W✓ OK (≤3%)
185 mm²353 A275 A3.16 V (0.76%)411.8 V5.21 V (1.25%)246.0 W✓ OK (≤3%)
240 mm²415 A324 A2.43 V (0.59%)412.6 V4.01 V (0.97%)189.6 W✓ OK (≤3%)
300 mm²477 A372 A1.95 V (0.47%)413.1 V3.21 V (0.77%)151.7 W✓ OK (≤3%)
400 mm²570 A445 A1.46 V (0.35%)413.5 V2.41 V (0.58%)113.8 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 45A at 350 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 50 mm² copper cable for 45A over 350m at 415V (voltage drop: 11.68V or 2.81%).

What is the power capacity of 45A at 415V?

At unity power factor, 45A at 415V supports 32.35 kW with a standard 45A circuit breaker.