475 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 475 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 7.71V (1.85%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 25.41V (6.12%)
Voltage at Load407.3 VLine Loss: 6337.2 W
Max Power & Breaker341.43 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4108.14 V (989.91%)0.0 V6776.5 V (1632.89%)3379862.5 WDrop High
2.5 mm²24 A18 A2464.88 V (593.95%)0.0 V4065.9 V (979.74%)2027917.5 WDrop High
4 mm²32 A25 A1540.55 V (371.22%)0.0 V2541.19 V (612.33%)1267448.4 WDrop High
6 mm²41 A32 A1027.03 V (247.48%)0.0 V1694.13 V (408.22%)844965.6 WDrop High
10 mm²57 A44 A616.22 V (148.49%)0.0 V1016.48 V (244.93%)506979.4 WDrop High
16 mm²76 A59 A385.14 V (92.8%)29.9 V635.3 V (153.08%)316862.1 WDrop High
25 mm²101 A78 A246.49 V (59.39%)168.5 V406.59 V (97.97%)202791.7 WDrop High
35 mm²125 A97 A176.06 V (42.42%)238.9 V290.42 V (69.98%)144851.2 WDrop High
50 mm²151 A118 A123.24 V (29.7%)291.8 V203.3 V (48.99%)101395.9 WDrop High
70 mm²192 A150 A88.03 V (21.21%)327.0 V145.21 V (34.99%)72425.6 WDrop High
95 mm²232 A181 A64.87 V (15.63%)350.1 V107.0 V (25.78%)53366.2 WDrop High
120 mm²269 A210 A51.35 V (12.37%)363.6 V84.71 V (20.41%)42248.3 WDrop High
150 mm²309 A241 A41.08 V (9.9%)373.9 V67.77 V (16.33%)33798.6 WDrop High
185 mm²353 A275 A33.31 V (8.03%)381.7 V54.94 V (13.24%)27404.3 WDrop High
240 mm²415 A324 A25.68 V (6.19%)389.3 V42.35 V (10.21%)21124.1 WDrop High
300 mm²477 A372 A20.54 V (4.95%)394.5 V33.88 V (8.16%)16899.3 W~ ≤5%
400 mm²570 A445 A15.41 V (3.71%)399.6 V25.41 V (6.12%)12674.5 W~ ≤5%

FAQ — 475 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 475A at 350 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 475A over 350m at 415V (voltage drop: 7.71V or 1.85%).

What is the power capacity of 475A at 415V?

At unity power factor, 475A at 415V supports 341.43 kW with a standard 500A circuit breaker.