5 Amp Cable Size at 200 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 200 m (656.2 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 1.22V (2.55%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 1.41V (2.94%)
Voltage at Load46.8 VLine Loss: 6.1 W
Max Power & Breaker0.24 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A28.53 V (59.44%)19.5 V47.07 V (98.06%)142.7 WDrop High
2.5 mm²24 A18 A17.12 V (35.67%)30.9 V28.24 V (58.83%)85.6 WDrop High
4 mm²32 A25 A10.7 V (22.29%)37.3 V17.65 V (36.77%)53.5 WDrop High
6 mm²41 A32 A7.13 V (14.86%)40.9 V11.77 V (24.51%)35.7 WDrop High
10 mm²57 A44 A4.28 V (8.92%)43.7 V7.06 V (14.71%)21.4 WDrop High
16 mm²76 A59 A2.67 V (5.57%)45.3 V4.41 V (9.19%)13.4 WDrop High
25 mm²101 A78 A1.71 V (3.57%)46.3 V2.82 V (5.88%)8.6 W~ ≤5%
35 mm²125 A97 A1.22 V (2.55%)46.8 V2.02 V (4.2%)6.1 W✓ OK (≤3%)
50 mm²151 A118 A0.86 V (1.78%)47.1 V1.41 V (2.94%)4.3 W✓ OK (≤3%)
70 mm²192 A150 A0.61 V (1.27%)47.4 V1.01 V (2.1%)3.1 W✓ OK (≤3%)
95 mm²232 A181 A0.45 V (0.94%)47.5 V0.74 V (1.55%)2.3 W✓ OK (≤3%)
120 mm²269 A210 A0.36 V (0.74%)47.6 V0.59 V (1.23%)1.8 W✓ OK (≤3%)
150 mm²309 A241 A0.29 V (0.59%)47.7 V0.47 V (0.98%)1.4 W✓ OK (≤3%)
185 mm²353 A275 A0.23 V (0.48%)47.8 V0.38 V (0.8%)1.2 W✓ OK (≤3%)
240 mm²415 A324 A0.18 V (0.37%)47.8 V0.29 V (0.61%)0.9 W✓ OK (≤3%)
300 mm²477 A372 A0.14 V (0.3%)47.9 V0.24 V (0.49%)0.7 W✓ OK (≤3%)
400 mm²570 A445 A0.11 V (0.22%)47.9 V0.18 V (0.37%)0.5 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 200 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 5A at 200 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 5A over 200m at 48V (voltage drop: 1.22V or 2.55%).

What is the power capacity of 5A at 48V?

At unity power factor, 5A at 48V supports 0.24 kW with a standard 6A circuit breaker.