5 Amp Cable Size at 350 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)70 mm²Drop: 1.07V (2.23%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 1.3V (2.71%)
Voltage at Load46.9 VLine Loss: 5.3 W
Max Power & Breaker0.24 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A49.93 V (104.03%)0.0 V82.37 V (171.6%)249.7 WDrop High
2.5 mm²24 A18 A29.96 V (62.42%)18.0 V49.42 V (102.96%)149.8 WDrop High
4 mm²32 A25 A18.72 V (39.01%)29.3 V30.89 V (64.35%)93.6 WDrop High
6 mm²41 A32 A12.48 V (26.01%)35.5 V20.59 V (42.9%)62.4 WDrop High
10 mm²57 A44 A7.49 V (15.6%)40.5 V12.35 V (25.74%)37.4 WDrop High
16 mm²76 A59 A4.68 V (9.75%)43.3 V7.72 V (16.09%)23.4 WDrop High
25 mm²101 A78 A3.0 V (6.24%)45.0 V4.94 V (10.3%)15.0 WDrop High
35 mm²125 A97 A2.14 V (4.46%)45.9 V3.53 V (7.35%)10.7 W~ ≤5%
50 mm²151 A118 A1.5 V (3.12%)46.5 V2.47 V (5.15%)7.5 W~ ≤5%
70 mm²192 A150 A1.07 V (2.23%)46.9 V1.76 V (3.68%)5.3 W✓ OK (≤3%)
95 mm²232 A181 A0.79 V (1.64%)47.2 V1.3 V (2.71%)3.9 W✓ OK (≤3%)
120 mm²269 A210 A0.62 V (1.3%)47.4 V1.03 V (2.14%)3.1 W✓ OK (≤3%)
150 mm²309 A241 A0.5 V (1.04%)47.5 V0.82 V (1.72%)2.5 W✓ OK (≤3%)
185 mm²353 A275 A0.4 V (0.84%)47.6 V0.67 V (1.39%)2.0 W✓ OK (≤3%)
240 mm²415 A324 A0.31 V (0.65%)47.7 V0.51 V (1.07%)1.6 W✓ OK (≤3%)
300 mm²477 A372 A0.25 V (0.52%)47.8 V0.41 V (0.86%)1.2 W✓ OK (≤3%)
400 mm²570 A445 A0.19 V (0.39%)47.8 V0.31 V (0.64%)0.9 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 350 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 5A at 350 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 70 mm² copper cable for 5A over 350m at 48V (voltage drop: 1.07V or 2.23%).

What is the power capacity of 5A at 48V?

At unity power factor, 5A at 48V supports 0.24 kW with a standard 6A circuit breaker.